Below is an example of a Calibration TEDS:
Calibration TEDS
Field # Description Field Length (Bytes) Field Type Field Contents
Data Structure related information
78 Calibration TEDS Length 4 U32 99
Calibration related information
79 Last Calibration Date-Time 4 U32 0
80 Calibration Interval 4 U8 0
81 Number of Correction Input Channels = n 1 U8 1
82 Correction Input Channel List 1 U8 1
83 Correction Input Channel-Key List 1 U8 0
84 Channel Degree List = D(k) 1 U8 1
85 Number of Segments List = Nk 1 U8 5
86 Segment Boundary Values Table (Pa) 24 F32 0
  (segment 1 high boundary)   F32 4136838
  (segment 2 high boundary)   F32 8273676
  (segment 3 high boundary)   F32 12410514
  (segment 4 high boundary)   F32 16547352
  (segment 5 high boundary)   F32 20684190
87 Segment Offset Values Table (Pa) 20    
  (segment 1 offset)   F32 5051
  (segment 2 offset)   F32 5051
  (segment 3 offset)   F32 5051
  (segment 4 offset)   F32 5051
  (segment 5 offset)   F32 5051
88 Multinomial Coefficients 40    
  A00 (Pa)   F32 -126372
  A01 (Pa/count)   F32 5244
  A10   F32 -44141
  A11   F32 5144
  A20   F32 111220
  A21   F32 5049
  A30   F32 331826
  A31   F32 4959
  A40   F32 610811
  A41   F32 4874
Data Integrity Information
89 Checksum for Calibration TEDS 2 U16 57092
 
Back to TEDS  