Skip to main content
U.S. flag

An official website of the United States government

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Secure .gov websites use HTTPS
A lock ( ) or https:// means you’ve safely connected to the .gov website. Share sensitive information only on official, secure websites.

FCD Experiments

Search the title, description, test director, specimen, fuel type, and ignition.
Experiment Name Plot of Heat Release Rate Ignition Photo Date/Time Project Sort descending Specimen Fuel Type Total Heat Released (MJ) Peak HRR (kW)
Test098_RadPlank_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
radiant panel ON (but covered)
Transient Combustion Calorimetry (TCC) wood plank Cellulose
below detection limit
0.73
Test051_FRtarp15x10_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic tarp Plastic
53.7
50.6
Test002_EmptyBox1ft_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) empty cardboard box Cellulose
5.97
158.8
Test067_TrashCanQuarter_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Rubber trash can Plastic
138.4
276
Test019_SilverTarp_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic tarp Plastic
36.1
200
Test083_GardenHose_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Rubber hose Rubber
0.68
1.57
Test035_WelderExtCord8awg_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) electric cord Plastic
0.25
1.36
Test099_RadPlank_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
radiant panel ON (but covered)
Transient Combustion Calorimetry (TCC) wood plank Cellulose
0.97
1.81
Test052_FRtarp15x10_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic tarp Plastic
54.4
83.0
Test003_5HeptaneRags_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) cotton rags soaked with heptane Cellulose
6.44
46.8
Test068_TrashCanHalf_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Rubber trash can Plastic
152.2
377
Test020_SilverTarp_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic tarp Plastic
36.0
71.0
Test084_PatioChair_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic chair Plastic
103.7
209
Test036_WelderExtCord8awg_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) electric cord Plastic
below detection limit
1.03
Test100_RadPlank_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
radiant panel ON
Transient Combustion Calorimetry (TCC) wood plank Cellulose
below detection limit
0.89
Test053_CanvasTarp12x12_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) canvas tarp Cellulose
51.6
499
Test004_EmptyBox1ft_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) empty cardboard box Cellulose
6.04
136.1
Test069_TrashCanFull_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Rubber trash can Plastic
171
281
Test021_WeldingBlanket_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) welding blanket Fiberglass
0.149
2.31
Test085_PatioChair_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic chair Plastic
102.6
159.9

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314