| Name | Test067_TrashCanQuarter_R2 | 
|---|---|
| Date |  | 
| Description | 32 gal Plastic can w/ 314g paper, 5 clear water bottles. Ignition=wick soaked w/ 5 mL heptane | 
| Specimen | Rubber trash can | 
| Ignition | heptane wick | 
| Project ID (s) | |
| Test Director | McGrattan | 
| Measurement | Value | Uc | Unit | 
|---|---|---|---|
| Peak Heat Release Rate, PHRR | 276 | 16 | kW | 
| Time to Peak Heat Release Rate | 18.22 | 0.17 | min | 
| Total Heat Released, THR | 138.4 | 8.5 | MJ | 
| Gas Burner Total Heat Released, NGTHR | -1 | - | MJ | 
| Heat Release Quality Confirmation, HRQC | Not measured | - | MJ/MJ | 
| Net Specimen Mass (gravimetric), NM = Mi-Mf | 3.685 | 0.028 | kg | 
| Net Effective Heat of Combustion = THR / NM | 37.6 | 2.3 | MJ/kg | 
| O2 Yield = O2 Consumed / NM | 2.704 | 0.089 | kg/kg | 
| CO2 Yield = CO2 Generated / NM | 2.644 | 0.097 | kg/kg | 
| CO Yield = CO Generated / NM | 0.01741 | 0.00064 | kg/kg | 
| Soot Yield = Soot Generated / NM | 0.0433 | 0.0057 | kg/kg | 
| Baseline Hood Exhaust Flow | 3.091 | 0.093 | kg/s | 
| Test Duration = Time(Fire Out) - Time(Ignition) | 39.97 | 0.03 | min | 
Uc = Combined Expanded Uncertainty with 95% confidence level
| Parameter | Value | Uc | Unit | 
|---|---|---|---|
| Fuel Type | Plastic | - | - | 
| Hood Size | 3 | - | m | 
| Effective Duct Diameter | 0.485 | 0.005 | m | 
| Exhaust Flow Correction Factor | 1.033 | 0.029 | - | 
| Net Heat of Combustion (per unit mass O2), Ef | 13.10 | 0.66 | MJ/kg | 
| Net Heat of Combustion(per unit mass fuel), HOCf | 30.00 | 6.00 | MJ/kg | 
| Initial Specimen Mass, Mi (gravimetric) | 3.84 | 0.02 | kg | 
| Final Specimen Mass, Mf (gravimetric) | 0.16 | 0.02 | kg | 
 
    | Event | Time (min) | Description | Video Snapshot Image | 
|---|---|---|---|
| 1 | 0.00 | Ignition |   | 
| peak | 18.22 | Peak HRR |   | 
| 2 | 39.97 | Fire Out |   | 
 
     
     
     
     
     
    Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
        https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
        https://doi.org/10.18434/mds2-2314