Skip to main content
U.S. flag

An official website of the United States government

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Secure .gov websites use HTTPS
A lock ( ) or https:// means you’ve safely connected to the .gov website. Share sensitive information only on official, secure websites.

FCD Experiments

Search the title, description, test director, specimen, fuel type, and ignition.
Experiment Name Plot of Heat Release Rate Ignition Photo Date/Time Sort descending Project Specimen Fuel Type Total Heat Released (MJ) Peak HRR (kW)
Test100_RadPlank_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
radiant panel ON
Transient Combustion Calorimetry (TCC) wood plank Cellulose
below detection limit
0.89
Test101_PPEonShelf_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) gloves and coveralls Plastic
45.8
71.7
Test102_WorkCart_R1a
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) work cart with laptop and printer Plastic
716
2,704
Test103_PPEonShelf_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) gloves and coveralls Plastic
57.1
121.8
Test0104_BigEmptyBox2ft_R4
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) empty cardboard box Cellulose
25.8
468
Test0105_WorkCart_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) work cart with laptop and printer Plastic
712
2,503
Test0106_WorkCart_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) work cart with laptop and printer Plastic
702
2,240
NGCal_6m_3MW_16kgs
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) tube gas burner Natural Gas
1,932
3,159
NGCal_6m_3MW_16kgs
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Natural Gas Confirmation Burner tube gas burner Natural Gas
1,932
3,159
NGCal_3mHood_300kW_2kgs
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Natural Gas Confirmation Burner box gas burner Natural Gas
186.9
328
NGCal_3mHood_300kW_2kgs
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) box gas burner Natural Gas
186.9
328
Methanol_1m_Pool_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Characteristics of a 1 m Methanol Pool Fire 1 m diameter pool burner Methanol
753
282
Methanol_1m_Pool_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Characteristics of a 1 m Methanol Pool Fire 1 m diameter pool burner Methanol
1,243
279
15minRamp_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Steel-Concrete Composite Floor Systems Subject to Fire, Phase 2 Four square burners Natural Gas
5,047
8,034
15minRamp_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Steel-Concrete Composite Floor Systems Subject to Fire, Phase 2 Four square burners Natural Gas
4,850
7,980
60minRamp_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Steel-Concrete Composite Floor Systems Subject to Fire, Phase 2 Four square burners Natural Gas
37,631
10,317
NG_Ver_2MW_16kgs
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Natural Gas Confirmation Burner tube burner Natural Gas
1,329
2,050
Test1_PMMA_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
506
2,540
NGQC_3m_3kgs_500kW
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Natural Gas Confirmation Burner box gas burner Natural Gas
381
532
NGQC_9m_50kgs_8MWa
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Natural Gas Confirmation Burner tube gas burner Natural Gas
4,832
8,337

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314