Experiment Name Plot of Heat Release Rate Ignition Photo Date/Time Project Specimen Sort descending Fuel Type Total Heat Released (MJ) Peak HRR (kW)
Test_3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Room Flashover Experiments to Demonstrate the Effectiveness of Barrier Fabrics furnished room with cotton fabric sofa no barrier Cellulose, Plastic
2,636
9,639
Test_2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Room Flashover Experiments to Demonstrate the Effectiveness of Barrier Fabrics furnished room with cotton fabric sofa with barrier Cellulose, Plastic
2,246
8,422
Test_1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Room Flashover Experiments to Demonstrate the Effectiveness of Barrier Fabrics furnished room with polyester fabric sofa no barrier Cellulose, Plastic
2,551
9,175
CLT_Room_Test_1-1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Cross Laminated Timber Compartments furnished studio apartment Cellulose, Plastic
17,883
9,487
CLT_Room_Test_1-2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Cross Laminated Timber Compartments furnished studio apartment Cellulose, Plastic
18,541
12,451
CLT_Room_Test_1-4
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Cross Laminated Timber Compartments furnished studio apartment, CLT ceiling Cellulose, Plastic
35,941
13,114
CLT_Room_Test_1-3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Cross Laminated Timber Compartments furnished studio apartment, CLT wall Cellulose, Plastic
32,448
14,171
CLT_Room_Test_1-5
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Cross Laminated Timber Compartments furnished studio apartment, CLT wall Cellulose, Plastic
53,580
10,372
CLT_Room_Test_1-6
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Cross Laminated Timber Compartments furnished studio apartment, CLT wall and ceiling Cellulose, Plastic
78,200
12,910
Propane Burner Check
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Fire Barriers in Full-Scale Chair Mock-ups gas tube burner Propane
3.22
24.3
Gasoline_50g
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
fuel pour
Stovetop Cooking Pan Fire Safety gasoline in 20 cm pan Gasoline
2.04
21.9
Test037_PPEbagQuarter_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) gloves and coveralls Plastic
10.12
17.7
Test101_PPEonShelf_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) gloves and coveralls Plastic
45.8
71.7
Test038_PPEbagHalf_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) gloves and coveralls Plastic
24.6
30.1
Test039_PPEbagFull_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) gloves and coveralls Plastic
52.8
112.7
Test103_PPEonShelf_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) gloves and coveralls Plastic
57.1
121.8
Test040_PPEbagQuarter_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) gloves and coveralls Plastic
9.33
13.09
Test041_PPEbagHalf_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) gloves and coveralls Plastic
24.7
69.3
Test042_PPEbagFull_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) gloves and coveralls Plastic
51.4
114.8
Test043_PPEbagQuarter_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) gloves and coveralls Plastic
10.46
22.4

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)