| Name | CLT_Room_Test_1-6
|
|---|---|
| Date | |
| Description | Furnished room with 3 layers of type X gypsum on 3 walls. Wall 1 and ceiling is exposed CLT. Narrow door opening |
| Specimen | furnished studio apartment, CLT wall and ceiling
|
| Ignition | natural gas burner
|
| Project ID (s) | |
| Test Director | Hoehler
|
| Measurement | Value | Uc | Unit |
|---|---|---|---|
| Peak Heat Release Rate, PHRR
|
12,910
|
771
|
kW
|
| Time to Peak Heat Release Rate
|
10.38
|
0.17
|
min
|
| Total Heat Released, THR
|
78,200
|
4,729
|
MJ
|
| Natural Gas Burner Total Heat Released, NGTHR
|
24.97
|
0.36
|
MJ
|
| Heat Release Quality Confirmation, HRQC
|
below detection limit
|
0.000
|
MJ/MJ
|
| Net Specimen Mass (gravimetric), NM = Mi-Mf
|
Not measured | - | kg
|
| Total Fuel Mass Burned, TFM = THR / HOCf
|
3,930
|
459
|
kg
|
| Net Effective Heat of Combustion = THR / NM
|
Not measured | - | MJ/kg
|
| O2 Yield = O2 Consumed / TFM
|
1.56
|
0.19
|
kg/kg
|
| CO2 Yield = CO2 Generated / TFM
|
2.09
|
0.26
|
kg/kg
|
| CO Yield = CO Generated / TFM
|
0.0161
|
0.0020
|
kg/kg
|
| Soot Yield = Soot Generated / TFM
|
Not measured | - | kg/kg
|
| Baseline Hood Exhaust Flow
|
95.1
|
2.9
|
kg/s
|
| Test Duration = Time(Fire Out) - Time(Ignition)
|
192.53
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
| Parameter | Value | Uc | Unit |
|---|---|---|---|
| Fuel Type
|
Cellulose, Plastic
|
- | - |
| Hood Size
|
15
|
- | m
|
| Effective Duct Diameter
|
2.424
|
0.005
|
m
|
| Exhaust Flow Correction Factor
|
1.000
|
0.029
|
- |
| Net Heat of Combustion (per unit mass O2), Ef
|
13.10
|
0.66
|
MJ/kg
|
| Net Heat of Combustion(per unit mass fuel), HOCf
|
19.90
|
2.00
|
MJ/kg
|
| Initial Specimen Mass, Mi (gravimetric)
|
Not measured | - | kg
|
| Final Specimen Mass, Mf (gravimetric)
|
Not measured | - | kg
|
| Event | Time (min) | Description | Video Snapshot Image |
|---|---|---|---|
| 1
|
0.00
|
Ignition
|
|
| 2
|
9.83
|
room flashover
|
|
| peak
|
10.38
|
Peak HRR
|
|
| 3
|
159.92
|
suppress
|
|
| 4
|
192.53
|
Fire Out
|
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314