Evaluating Positive Pressure Ventilation In Large Structures: High-Rise Pressure Experiments(NISTIR 7412)

Published

Author(s)

Stephen Kerber, Daniel M. Madrzykowski, D W. Stroup

Abstract

One hundred and sixty experiments were conducted in a thirty-story vacant office building in Toledo, Ohio to evaluate the ability of fire department positive pressure ventilation fans to pressurize a stairwell in a high-rise structure in accordance with established performance metrics for fixed stairwell pressurization systems. Variables such as fan size, fan angle, setback distance, number of fans, orientation of fans, number of doors open and location of vents open were varied to examine capability and optimization of each. Fan size varied from 0.4 m (16 in) to 1.2 m (46 in). Fan angle ranged from 90 degrees to 80 degrees. The setback distance went from 0.6 m (2 ft) to 3.6 m (12 ft). Between one and nine fans were used which were located at three different exterior locations and three different interior locations. Fans were oriented both in series and in parallel configurations. Doors throughout the building were opened and closed to evaluate the effects. Finally a door to the roof and a roof hatch were used as vent points. The measurements taken during the experiments included differential pressure, air temperature, carbon monoxide, metrological data and sound levels.PPV fans utilized correctly can increase the effectiveness of fire fighters and survivability of occupants in high-rise buildings. In a high-rise building it is possible to increase the pressure of a stairwell to prevent the infiltration of smoke if fire crews configure the fans properly. Although many factors contribute and need to be considered for effective PPV operations, properly configured PPV can achieve stairwell pressures that are high enough to meet or exceed the performance metrics for fixed smoke control systems.
Citation
NIST Interagency/Internal Report (NISTIR) - 7412
Report Number
7412

Keywords

high rise buildings, ventilation, structures, experiments, office buildings, fire departments, fans, stairwells, pressurization, doors, vents, roofs, pressure, air temperature, carbon monoxide, noise (sound), effectiveness, fire fighters, survival, occupants, smoke, smoke control, weather effects, uncertainty

Citation

Kerber, S. , Madrzykowski, D. and Stroup, D. (2007), Evaluating Positive Pressure Ventilation In Large Structures: High-Rise Pressure Experiments(NISTIR 7412), NIST Interagency/Internal Report (NISTIR), National Institute of Standards and Technology, Gaithersburg, MD, [online], https://tsapps.nist.gov/publication/get_pdf.cfm?pub_id=861427 (Accessed March 29, 2024)