| Name | e17_SVSl0-5
|
|---|---|
| Date | |
| Description | Experiment test #17: Steel, very small shed, low fuel load, 4 @ 1A cribs centered, zero wind flow, 5' structural separation. ini mass 80.426 kgs. |
| Specimen | wood cribs in steel shed
|
| Ignition | heptane pan
|
| Project ID (s) | |
| Test Director | Brown
|
| Measurement | Value | Uc | Unit |
|---|---|---|---|
| Peak Heat Release Rate, PHRR
|
1,352
|
84
|
kW
|
| Time to Peak Heat Release Rate
|
18.00
|
0.07
|
min
|
| Total Heat Released, THR
|
1,115
|
72
|
MJ
|
| Gas Burner Total Heat Released, NGTHR
|
0
|
- | MJ
|
| Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
| Net Specimen Mass (gravimetric), NM = Mi-Mf
|
Not measured | - | kg
|
| Total Fuel Mass Burned, TFM = THR / HOCf
|
69.2
|
6.1
|
kg
|
| Net Effective Heat of Combustion = THR / NM
|
Not measured | - | MJ/kg
|
| O2 Yield = O2 Consumed / TFM
|
1.19
|
0.11
|
kg/kg
|
| CO2 Yield = CO2 Generated / TFM
|
1.52
|
0.15
|
kg/kg
|
| CO Yield = CO Generated / TFM
|
0.0170
|
0.0016
|
kg/kg
|
| Soot Yield = Soot Generated / TFM
|
0.00174
|
0.00028
|
kg/kg
|
| Baseline Hood Exhaust Flow
|
50.0
|
1.5
|
kg/s
|
| Test Duration = Time(Fire Out) - Time(Ignition)
|
28.27
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
| Parameter | Value | Uc | Unit |
|---|---|---|---|
| Fuel Type
|
Cellulose
|
- | - |
| Hood Size
|
15
|
- | m
|
| Effective Duct Diameter
|
2.424
|
0.009
|
m
|
| Exhaust Flow Correction Factor
|
1.042
|
0.032
|
- |
| Net Heat of Combustion (per unit mass O2), Ef
|
13.61
|
0.68
|
MJ/kg
|
| Net Heat of Combustion(per unit mass fuel), HOCf
|
16.12
|
1.00
|
MJ/kg
|
| Initial Specimen Mass, Mi (gravimetric)
|
80.43
|
0.10
|
kg
|
| Final Specimen Mass, Mf (gravimetric)
|
Not measured | - | kg
|
| Event | Time (min) | Description | Video Snapshot Image |
|---|---|---|---|
| 1
|
0.00
|
Ignition
|
|
| 2
|
4.87
|
Embers thru vent
|
|
| 3
|
10.55
|
partial vent activation
|
|
| peak
|
18.00
|
Peak HRR
|
|
| 4
|
25.02
|
water suppression
|
|
| 5
|
28.27
|
Fire Out
|
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)