| Name | FEWC213
|
|---|---|
| Date | |
| Description | Burning 2 gel packs. |
| Specimen | Wood Crib
|
| Ignition | propane wand
|
| Project ID (s) | |
| Test Director | Bryant
|
| Measurement | Value | Uc | Unit |
|---|---|---|---|
| Peak Heat Release Rate, PHRR
|
28.9
|
1.9
|
kW
|
| Time to Peak Heat Release Rate
|
1.98
|
0.07
|
min
|
| Total Heat Released, THR
|
4.07
|
0.32
|
MJ
|
| Gas Burner Total Heat Released, NGTHR
|
-2
|
- | MJ
|
| Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
| Net Specimen Mass (gravimetric), NM = Mi-Mf
|
0.100
|
0.042
|
kg
|
| Net Effective Heat of Combustion = THR / NM
|
41
|
17
|
MJ/kg
|
| O2 Yield = O2 Consumed / NM
|
2.9
|
1.2
|
kg/kg
|
| CO2 Yield = CO2 Generated / NM
|
2.7
|
1.1
|
kg/kg
|
| CO Yield = CO Generated / NM
|
0.0169
|
0.0084
|
kg/kg
|
| Soot Yield = Soot Generated / NM
|
0.056
|
0.025
|
kg/kg
|
| Baseline Hood Exhaust Flow
|
2.155
|
0.065
|
kg/s
|
| Test Duration = Time(Fire Out) - Time(Ignition)
|
11.58
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
| Parameter | Value | Uc | Unit |
|---|---|---|---|
| Fuel Type
|
Generic
|
- | - |
| Hood Size
|
3
|
- | m
|
| Effective Duct Diameter
|
0.483
|
0.004
|
m
|
| Exhaust Flow Correction Factor
|
1.033
|
0.029
|
- |
| Net Heat of Combustion (per unit mass O2), Ef
|
13.10
|
0.66
|
MJ/kg
|
| Net Heat of Combustion(per unit mass fuel), HOCf
|
30.00
|
0.90
|
MJ/kg
|
| Initial Specimen Mass, Mi (gravimetric)
|
0.10
|
0.03
|
kg
|
| Final Specimen Mass, Mf (gravimetric)
|
below detection limit
|
0.03
|
kg
|
| Event | Time (min) | Description | Video Snapshot Image |
|---|---|---|---|
| 1
|
0.00
|
Ignition
|
|
| peak
|
1.98
|
Peak HRR
|
|
| 2
|
11.58
|
Fire Out
|
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314