Experiment Name Plot of Heat Release Rate Ignition Photo Date/Time Sort descending Project Specimen Fuel Type Total Heat Released (MJ) Peak HRR (kW)
Test_39
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
9.04
73.4
Test_40
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
425
134.3
Test_41
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
661
219
Test_42
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
116.0
215
Test_43
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
343
332
Test_44
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
325
Test_45
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
157
56.1
Test_46
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
50.4
110.0
Test_47
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
24.3
90.2
Test_48
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
11.60
70.7
Test_49
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
366
219
Test_50
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
411
503
Test_51
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
176
209
Test_52
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
131.7
214
Test_53
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
142.7
284
Test_54
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
173
199
Test_55
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
147.3
227
Test_56
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
173
196
Test_57
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
464
283
Test_58
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
357
283

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314