Experiment Name | Plot of Heat Release Rate | Ignition Photo | Date/Time | Project | Specimen | Fuel Type Sort descending | Total Heat Released (MJ) | Peak HRR (kW) |
---|---|---|---|---|---|---|---|---|
Test30_2trashCanRagsPaper_r1 | Multiple Item Transient Combustion Calorimetry | plastic trashcan filled with cotton rags and paper | Cellulose, Plastic | 370
|
462
|
|||
CLT_Room_Test_1-3 | Cross Laminated Timber Compartments | furnished studio apartment, CLT wall | Cellulose, Plastic | 32,448
|
14,171
|
|||
Test011_BigBoxPeanuts 2ft_R2 | Transient Combustion Calorimetry (TCC) | cardboard and expanded polystyrene (EPS) peanuts | Cellulose, Plastic | 37.3
|
600
|
|||
Test31_4trashCanRagsPaper_r1 | Multiple Item Transient Combustion Calorimetry | plastic trashcan filled with cotton rags and paper | Cellulose, Plastic | 772
|
972
|
|||
CLT_Room_Test_1-4 | Cross Laminated Timber Compartments | furnished studio apartment, CLT ceiling | Cellulose, Plastic | 35,941
|
13,114
|
|||
CLT_Room_Test_1-5 | Cross Laminated Timber Compartments | furnished studio apartment, CLT wall | Cellulose, Plastic | 53,580
|
10,372
|
|||
Test17_Trashcan_r1 | Multiple Item Transient Combustion Calorimetry | plastic trashcans filled with paper | Cellulose, Plastic | 131
|
159
|
|||
CLT_Room_Test_1-6 | Cross Laminated Timber Compartments | furnished studio apartment, CLT wall and ceiling | Cellulose, Plastic | 78,200
|
12,910
|
|||
Test015_BigBoxPeanuts2ft_R3 | Transient Combustion Calorimetry (TCC) | cardboard and expanded polystyrene (EPS) peanuts | Cellulose, Plastic | 38.0
|
595
|
|||
Test18_2Trashcan_r1 | Multiple Item Transient Combustion Calorimetry | plastic trashcans filled with paper | Cellulose, Plastic | 257
|
445
|
|||
WateredTree3 | Dry Tree Fire Hazard | watered pine tree, upholstered chair and shelf in room corner | Cellulose, Plastic | below detection limit
|
6.7
|
|||
Test19_4Trashcan_r1 | Multiple Item Transient Combustion Calorimetry | plastic trashcans filled with paper | Cellulose, Plastic | 512
|
587
|
|||
Test36_2Trashcan_r2 | Multiple Item Transient Combustion Calorimetry | plastic trashcan with crinkle paper | Cellulose, Plastic | 253
|
409
|
|||
Dry_Pine_Tree | Dry Tree Fire Hazard | dry pine tree, upholstered chair and shelf in room corner | Cellulose, Plastic | 938
|
7,362
|
|||
Kitchen Room Fire | Kitchen Room Fire | kitchen room with OSB back wall | Cellulose, Plastic | 6,813
|
7,585
|
|||
Test20_4Trashcan2pallet_r1 | Multiple Item Transient Combustion Calorimetry | wood pallets and plastic trashcans with paper | Cellulose, Plastic | 1,028
|
2,319
|
|||
Test40_4Commodity_R2 | Multiple Item Transient Combustion Calorimetry | cardboard boxes filled with polystyrene cups | Cellulose, Polystyrene | 710
|
2,071
|
|||
Test25_1plasticCommodity_r1 | Multiple Item Transient Combustion Calorimetry | cardboard boxes filled with polystyrene cups | Cellulose, Polystyrene | 174
|
619
|
|||
Test26_2plasticCommodity_r1 | Multiple Item Transient Combustion Calorimetry | cardboard boxes filled with polystyrene cups | Cellulose, Polystyrene | 355
|
888
|
|||
Test27_4plasticCommodity_r1 | Multiple Item Transient Combustion Calorimetry | cardboard boxes filled with polystyrene cups | Cellulose, Polystyrene | 700
|
1,430
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314