Search the title, description, test director, specimen, fuel type, and ignition.
Experiment Name Plot of Heat Release Rate Ignition Photo Date/Time Project Specimen Fuel Type Sort descending Total Heat Released (MJ) Peak HRR (kW)
Test30_2trashCanRagsPaper_r1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry plastic trashcan filled with cotton rags and paper Cellulose, Plastic
370
462
CLT_Room_Test_1-3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Cross Laminated Timber Compartments furnished studio apartment, CLT wall Cellulose, Plastic
32,448
14,171
Test011_BigBoxPeanuts 2ft_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) cardboard and expanded polystyrene (EPS) peanuts Cellulose, Plastic
37.3
600
Test31_4trashCanRagsPaper_r1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry plastic trashcan filled with cotton rags and paper Cellulose, Plastic
772
972
CLT_Room_Test_1-4
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Cross Laminated Timber Compartments furnished studio apartment, CLT ceiling Cellulose, Plastic
35,941
13,114
CLT_Room_Test_1-5
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Cross Laminated Timber Compartments furnished studio apartment, CLT wall Cellulose, Plastic
53,580
10,372
Test17_Trashcan_r1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry plastic trashcans filled with paper Cellulose, Plastic
131
159
CLT_Room_Test_1-6
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Cross Laminated Timber Compartments furnished studio apartment, CLT wall and ceiling Cellulose, Plastic
78,200
12,910
Test015_BigBoxPeanuts2ft_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) cardboard and expanded polystyrene (EPS) peanuts Cellulose, Plastic
38.0
595
Test18_2Trashcan_r1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry plastic trashcans filled with paper Cellulose, Plastic
257
445
WateredTree3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Dry Tree Fire Hazard watered pine tree, upholstered chair and shelf in room corner Cellulose, Plastic
below detection limit
6.7
Test19_4Trashcan_r1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry plastic trashcans filled with paper Cellulose, Plastic
512
587
Test36_2Trashcan_r2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry plastic trashcan with crinkle paper Cellulose, Plastic
253
409
Dry_Pine_Tree
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Dry Tree Fire Hazard dry pine tree, upholstered chair and shelf in room corner Cellulose, Plastic
938
7,362
Kitchen Room Fire
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Kitchen Room Fire kitchen room with OSB back wall Cellulose, Plastic
6,813
7,585
Test20_4Trashcan2pallet_r1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry wood pallets and plastic trashcans with paper Cellulose, Plastic
1,028
2,319
Test40_4Commodity_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry cardboard boxes filled with polystyrene cups Cellulose, Polystyrene
710
2,071
Test25_1plasticCommodity_r1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry cardboard boxes filled with polystyrene cups Cellulose, Polystyrene
174
619
Test26_2plasticCommodity_r1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry cardboard boxes filled with polystyrene cups Cellulose, Polystyrene
355
888
Test27_4plasticCommodity_r1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry cardboard boxes filled with polystyrene cups Cellulose, Polystyrene
700
1,430

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314