Search the title, description, test director, specimen, fuel type, and ignition.
Experiment Name Plot of Heat Release Rate Ignition Photo Date/Time Project Specimen Fuel Type Total Heat Released (MJ) Peak HRR (kW) Sort ascending
Test4_PMMA_R4
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
504
3,140
1B-SVSh0-5_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Structure Separation Experiments: Shed Burns without Wind Steel Shed Wood Cribs Cellulose
956
3,123
Test52_HIPS_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of HIPS High Impact Polystyrene (HIPS)
535
3,094
NGQC_6m_20kgs_3MW
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry tube gas burner Natural Gas
2,372
3,094
NGQC_6m_20kgs_3MW
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Natural Gas Confirmation Burner tube gas burner Natural Gas
2,372
3,094
GasBurner_Flow50kgs_8MW
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Structure Separation Experiments: Shed Burns without Wind Tube Burner Natural Gas
965
3,050
NGQC_6m_20kgs_3MW
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Natural Gas Confirmation Burner tube gas burner Natural Gas
2,127
3,022
NGQC_6m_20kgs_3MW
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels tube gas burner Natural Gas
2,127
3,022
Test45_HIPS_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of HIPS High Impact Polystyrene (HIPS)
509
2,955
Test2_PMMA_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
506
2,882
Test59_XLPE4_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of XLPE foam (4lb/ft3 density) Cross-linked polyethylene foam (XLPE)
149.1
2,876
C0-1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Fire Barriers in Full-Scale Chair Mock-ups upholstered chair mockup Polyurethane Foam
315
2,834
Test60_XLPE4_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of XLPE foam (4lb/ft3 density) Cross-linked polyethylene foam (XLPE)
174.4
2,830
Test28_8plasticCommodity_r1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry cardboard boxes filled with polystyrene cups Cellulose, Polystyrene
1,438
2,826
Test12_PBT_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of PBT Polybutylene terephthalate (PBT)
375
2,821
Test16_HDPE_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of HDPE High Density Polyethelyne (HDPE)
284
2,817
1B-WC00-0
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Structure Separation Experiments: Shed Burns without Wind Wood Shed Cellulose
772
2,784
1B-SVSh0-5
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Structure Separation Experiments: Shed Burns without Wind Steel Shed Wood Cribs Cellulose
780
2,711
Test102_WorkCart_R1a
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) work cart with laptop and printer Plastic
716
2,704
C0-2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Fire Barriers in Full-Scale Chair Mock-ups upholstered chair mockup Polyurethane Foam
325
2,697

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)