Experiment Name Plot of Heat Release Rate Ignition Photo Date/Time Sort descending Project Specimen Fuel Type Total Heat Released (MJ) Peak HRR (kW)
Test37_4box_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry cardboard boxes filled with paper Cellulose
459
930
Test38_4box_R4
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry cardboard boxes filled with paper Cellulose
471
1,964
Test39_4trashcan_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry trashcans filled with paper Cellulose, Plastic
453
705
Test40_4Commodity_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry cardboard boxes filled with polystyrene cups Cellulose, Polystyrene
710
2,071
NGQC_6m_20kgs_3MW
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Natural Gas Confirmation Burner tube gas burner Natural Gas
2,462
3,140
NGQC_9m_50kgs_8MW
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Natural Gas Confirmation Burner tube gas burner Natural Gas
4,064
8,454
NGQC_15m_75kgs_12MW
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Natural Gas Confirmation Burner tube gas burner Natural Gas
3,844
8,243
Test_1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Room Flashover Experiments to Demonstrate the Effectiveness of Barrier Fabrics furnished room with polyester fabric sofa no barrier Cellulose, Plastic
2,551
9,175
Test_2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Room Flashover Experiments to Demonstrate the Effectiveness of Barrier Fabrics furnished room with cotton fabric sofa with barrier Cellulose, Plastic
2,246
8,422
Test_3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Room Flashover Experiments to Demonstrate the Effectiveness of Barrier Fabrics furnished room with cotton fabric sofa no barrier Cellulose, Plastic
2,636
9,639
NGQC_3m_2kgs_400kW_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Natural Gas Confirmation Burner box burner Natural Gas
307.8
438
Throw_pillow_1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Room Flashover Experiments to Demonstrate the Effectiveness of Barrier Fabrics Throw Pillow Polyester
3.96
34.6
Throw_pillow_2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Room Flashover Experiments to Demonstrate the Effectiveness of Barrier Fabrics Throw Pillow Polyester
4.20
45.0
BurnerShakedownO1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels sand burner box Propane
37.7
71.2
Test15_RedCedar_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 7/8" thick, 22.5" wide, 96" tall planks of Western Red Cedar Western Red Cedar
139
307
Test16_HDPE_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of HDPE High Density Polyethelyne (HDPE)
284
2,817
Test17_GPO1_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of GPO-1 Polyester resin (GPO-1)
235
498
Test18_XLPE2_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of XLPE Foam (2lb/ft3 density) Cross-linked polyethylene foam (XLPE)
101.4
3,992
Test19_XLPE6_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of XLPE Foam (6lb/ft3 density) Cross-linked polyethylene foam (XLPE)
278
3,500
BSEE_Test_001
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
gravel burner Methane
18.4
39.1

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314