NGQC_3m_2kgs_400kW_R3

Table 1. Test Information
Name
NGQC_3m_2kgs_400kW_R3
Date
Description

Natural gas confirmation using flamechannel burner with 30 cm square opening

Specimen
box burner
Ignition
propane wand
Project ID (s)
Test Director
Bryant

Timelapse Video with Heat Release Rate Plot

Table 2. Summary of Test Results
Measurement Value Uc Unit
Peak Heat Release Rate, PHRR
438
14
kW
Time to Peak Heat Release Rate
17.52
0.17
min
Total Heat Released, THR
307.8
9.9
MJ
Natural Gas Burner Total Heat Released, NGTHR
300.3
4.1
MJ
Heat Release Quality Confirmation, HRQC
1.020
0.035
MJ/MJ
Net Specimen Mass (gravimetric), NM = Mi-Mf
Not measured -
kg
Total Fuel Mass Burned, TFM = THR / HOCf
6.16
0.21
kg
Net Effective Heat of Combustion = THR / NM
Not measured -
MJ/kg
O2 Yield = O2 Consumed / TFM
3.68
0.17
kg/kg
CO2 Yield = CO2 Generated / TFM
2.85
0.14
kg/kg
CO Yield = CO Generated / TFM
below detection limit
0.00035
kg/kg
Soot Yield = Soot Generated / TFM
below detection limit
0.00082
kg/kg
Baseline Hood Exhaust Flow
2.111
0.063
kg/s
Test Duration = Time(Fire Out) - Time(Ignition)
24.80
0.03
min

Uc = Combined Expanded Uncertainty with 95% confidence level

Table 3. Summary of Test Input Parameters
Parameter Value Uc Unit
Fuel Type
Natural Gas
- -
Hood Size
3
-
m
Effective Duct Diameter
0.483
0.004
m
Exhaust Flow Correction Factor
1.033
0.029
-
Net Heat of Combustion (per unit mass O2), Ef
12.54
0.04
MJ/kg
Net Heat of Combustion(per unit mass fuel), HOCf
50.00
0.60
MJ/kg
Initial Specimen Mass, Mi (gravimetric)
Not measured -
kg
Final Specimen Mass, Mf (gravimetric)
Not measured -
kg
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Figure 1. Plot of Heat Release Rate data with event markers and error bars shown at peak.
Table 4. Summary of Observed Test Events
Event Time (min) Description Video Snapshot Image
1
0.00
Ignition
Ignition
2
2.40
105 kW
105 kW
3
6.55
297 kW
297 kW
4
11.35
210 kW
210 kW
5
16.18
415 kW
415 kW
peak
17.52
Peak HRR
Peak HRR
6
20.50
54 kW
54 kW
7
24.80
Fire Out
Fire Out

Table 5. Supplemental Data Plots

Plot of Oxygen Dry Volume Fraction in hood exhaust stream.
Plot of Oxygen Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Dioxide Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Dioxide Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Monoxide Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Monoxide Dry Volume Fraction in hood exhaust stream.
Plot of Radiant Heat Flux data with event markers. r= radial distance from center of hood, h=height above floor.
Plot of Radiant Heat Flux data with event markers. r= radial distance from center of hood, h=height above floor.
Plot of Smoke Laser Extinction Coefficient in hood exhaust stream.
Plot of Smoke Laser Extinction Coefficient in hood exhaust stream.
Plot of Exhaust Duct Mass Flow Rate.
Plot of Exhaust Duct Mass Flow Rate.

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077