Experiment Name Plot of Heat Release Rate Ignition Photo Date/Time Project Specimen Fuel Type Sort ascending Total Heat Released (MJ) Peak HRR (kW)
Control-Smoldering
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Fire Barriers in Full-Scale Chair Mock-ups upholstered chair mockup Polyurethane Foam
below detection limit
9.4
C0-3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Fire Barriers in Full-Scale Chair Mock-ups upholstered chair mockup Polyurethane Foam
321
2,517
B4-1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Fire Barriers in Full-Scale Chair Mock-ups upholstered chair mockup Polyurethane Foam
310
2,084
C0-1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Fire Barriers in Full-Scale Chair Mock-ups upholstered chair mockup Polyurethane Foam
315
2,834
B6-1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Fire Barriers in Full-Scale Chair Mock-ups upholstered chair mockup Polyurethane Foam
301
1,080
1B-PCl0
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Structure Separation Experiments: Shed Burns without Wind PP Shed Wood Cribs Polypropylene and Cellulose
1,542
3,220
Test61_POMGF_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of POM-GF Polyoxymethylene (POM-GF)
452
536
Test28_POMGF_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of POM-GF Polyoxymethylene (POM-GF)
387
503
Test50_POMGF_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of POM-GF Polyoxymethylene (POM-GF)
367
540
Test4_PMMA_R4
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
504
3,140
Test5_PMMA_R5
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
504
3,166
Test7_PMMA_R6
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
503
3,579
Test1_PMMA_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
506
2,540
Test2_PMMA_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
506
2,882
Test3_PMMA_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
506
3,197
Test21_Polyiso_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
28.6
949
Test44_Polyiso05_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/2" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
17.9
1,022
Test24_Polyiso_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
32.0
974
Test25_Polyiso_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
gas on
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
31.0
954
Test26_Polyiso2_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
gas on
Vertical Upward Flamespread on Parallel Panels 2" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
37.6
784

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077