Skip to main content
U.S. flag

An official website of the United States government

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Secure .gov websites use HTTPS
A lock ( ) or https:// means you’ve safely connected to the .gov website. Share sensitive information only on official, secure websites.

FCD Experiments

Search the title, description, test director, specimen, fuel type, and ignition.
Experiment Name Plot of Heat Release Rate Ignition Photo Date/Time Project Specimen Sort descending Fuel Type Total Heat Released (MJ) Peak HRR (kW)
Test32_Polyiso05_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/2" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
18.2
997
Test44_Polyiso05_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/2" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
17.9
1,022
Test14_Redboard_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 48" tall panels of GPO-3 Glass-reinforced polyester resin (GPO-3, 'Redboard')
36.2
109.6
Test53_ABS_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of ABS Acrylonitrile Butadiene Styrene (ABS)
550
3,541
Test51_ABS_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of ABS Acrylonitrile Butadiene Styrene (ABS)
566
3,538
Test47_ABS_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of ABS Acrylonitrile Butadiene Styrene (ABS)
547
3,821
Test2_PMMA_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
506
2,882
Test3_PMMA_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
506
3,197
Test4_PMMA_R4
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
504
3,140
Test5_PMMA_R5
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
504
3,166
Test7_PMMA_R6
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
503
3,579
Test1_PMMA_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
506
2,540
Test49_GPO1_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of GPO-1 Polyester resin (GPO-1)
232
522
Test17_GPO1_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of GPO-1 Polyester resin (GPO-1)
235
498
Test40_GPO1_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of GPO-1 Glass-reinforced polyester resin (GPO-1)
246
469
Test6_Redboard_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of GPO-3 Polyester resin (GPO-3, Redboard)
43.0
134.3
Test8_Redboard_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of GPO-3 Polyester resin (GPO-3, Redboard)
37.8
114.9
Test16_HDPE_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of HDPE High Density Polyethelyne (HDPE)
284
2,817
Test56_HIPS_R4
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of HIPS High Impact Polystyrene (HIPS)
513
3,173
Test52_HIPS_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of HIPS High Impact Polystyrene (HIPS)
535
3,094

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)