Table 1. Test Information
Name
Test56_HIPS_R4
Date
Description

1/4" thick, 24" wide, 96"tall panels of Hips mounted to 1" thick Marinite Board. Ignite using propane burner at 65kW, burner shut off and shielded after sustained flaming of panels.

Specimen
1/4" thick, 24" wide, 96" tall panels of HIPS
Ignition
propane buner
Project ID (s)
Test Director
Leventon

Timelapse Video with Heat Release Rate Plot

Table 2. Summary of Test Results
Measurement Value Uc Unit
Peak Heat Release Rate, PHRR
3,173
163
kW
Time to Peak Heat Release Rate
3.50
0.17
min
Total Heat Released, THR
513
32
MJ
Gas Burner Total Heat Released, NGTHR
4.68
0.14
MJ
Heat Release Quality Confirmation, HRQC
Not measured -
MJ/MJ
Net Specimen Mass (gravimetric), NM = Mi-Mf
17.88
0.28
kg
Net Effective Heat of Combustion = THR / NM
28.7
1.9
MJ/kg
O2 Yield = O2 Consumed / NM
2.160
0.077
kg/kg
CO2 Yield = CO2 Generated / NM
2.108
0.083
kg/kg
CO Yield = CO Generated / NM
0.0627
0.0025
kg/kg
Soot Yield = Soot Generated / NM
0.200
0.028
kg/kg
Baseline Hood Exhaust Flow
22.36
0.67
kg/s
Test Duration = Time(Fire Out) - Time(Ignition)
66.20
0.03
min

Uc = Combined Expanded Uncertainty with 95% confidence level

Table 3. Summary of Test Input Parameters
Parameter Value Uc Unit
Fuel Type
High Impact Polystyrene (HIPS)
- -
Hood Size
6
-
m
Effective Duct Diameter
1.975
0.005
m
Exhaust Flow Correction Factor
1.028
0.029
-
Net Heat of Combustion (per unit mass O2), Ef
12.93
0.51
MJ/kg
Net Heat of Combustion(per unit mass fuel), HOCf
30.00
0.90
MJ/kg
Initial Specimen Mass, Mi (gravimetric)
19.70
0.20
kg
Final Specimen Mass, Mf (gravimetric)
1.82
0.20
kg
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Figure 1. Plot of Heat Release Rate data with event markers and error bars shown at peak.
Table 4. Summary of Observed Test Events
Event Time (min) Description Video Snapshot Image
1
0.00
Ignition
Ignition
2
1.47
shield burner from dripping plastic
shield burner from dripping plastic
3
2.75
pull HF gauge shields
pull HF gauge shields
peak
3.50
Peak HRR
Peak HRR
4
6.18
suppress fire behind panels with garden hose
suppress fire behind panels with garden hose
5
66.20
Fire Out
Fire Out

Table 5. Supplemental Data Plots

Plot of Oxygen Dry Volume Fraction in hood exhaust stream.
Plot of Oxygen Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Dioxide Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Dioxide Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Monoxide Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Monoxide Dry Volume Fraction in hood exhaust stream.
Plot of Radiant Heat Flux data with event markers. r= radial distance from center of hood, h=height above floor.
Plot of Radiant Heat Flux data with event markers. r= radial distance from center of hood, h=height above floor.
Plot of Smoke Laser Extinction Coefficient in hood exhaust stream.
Plot of Smoke Laser Extinction Coefficient in hood exhaust stream.
Plot of Exhaust Duct Mass Flow Rate.
Plot of Exhaust Duct Mass Flow Rate.

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314

Report Process Script Version
NFRL_Report_8.5.1
Last Updated November 8, 2023