Skip to main content
U.S. flag

An official website of the United States government

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Secure .gov websites use HTTPS
A lock ( ) or https:// means you’ve safely connected to the .gov website. Share sensitive information only on official, secure websites.

FCD Experiments

Search the title, description, test director, specimen, fuel type, and ignition.
Experiment Name Plot of Heat Release Rate Ignition Photo Date/Time Sort ascending Project Specimen Fuel Type Total Heat Released (MJ) Peak HRR (kW)
1B-WCh0
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Structure Separation Experiments: Shed Burns without Wind Wood Shed Wood Cribs Cellulose
2,110
4,171
GasBurner_Flow25kgs_4MW
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Structure Separation Experiments: Shed Burns without Wind Tube Burner Natural Gas
2,048
4,440
GasBurner_Flow50kgs_8MW
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Structure Separation Experiments: Shed Burns without Wind Tube Burner Natural Gas
965
3,050
CompositeFloorTest_No2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Steel-Concrete Composite Floor Systems Subject to Fire, Phase 2 Four square burners Natural Gas
86,908
12,776
Test52_HIPS_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of HIPS High Impact Polystyrene (HIPS)
535
3,094
Test51_ABS_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of ABS Acrylonitrile Butadiene Styrene (ABS)
566
3,538
Test50_POMGF_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of POM-GF Polyoxymethylene (POM-GF)
367
540
Test49_GPO1_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of GPO-1 Polyester resin (GPO-1)
232
522
Test48_XPSpink1_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of Pink XPS Foam Extruded Polystyrene Foam (XPS)
55.3
1,332
Test47_ABS_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of ABS Acrylonitrile Butadiene Styrene (ABS)
547
3,821
Test46_HIPS_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
NTP Time Query Failed!
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of HIPS High Impact Polystyrene (HIPS)
504
3,228
Test45_HIPS_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of HIPS High Impact Polystyrene (HIPS)
509
2,955
SSEgasBurner3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Structure Separation Experiments: Shed Burns without Wind box burner Natural Gas
1,268
1,019
SSEgasBurner2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Structure Separation Experiments: Shed Burns without Wind box burner Natural Gas
712
630
SSEgasBurner1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Structure Separation Experiments: Shed Burns without Wind box burner Natural Gas
742
713
SSEgasBurner0
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Structure Separation Experiments: Shed Burns without Wind box burner Natural Gas
311
418
Test44_Polyiso05_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/2" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
17.9
1,022
Test43_RedCedar_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 7/8" thick, 22.5" wide, 96" tall planks of Western Red Cedar Western Red Cedar
38.8
398
Test42_XPSGreen2_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 2" thick, 24" wide, 96" tall panels of Green XPS Foam Extruded Polystyrene Foam (XPS)
105
1,946
Test41_XPSPink2_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 2" thick, 24" wide, 96" tall panels of Pink XPS Foam Extruded Polystyrene Foam (XPS)
100.6
1,687

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)