| Name | SSEgasBurner1
|
|---|---|
| Date | |
| Description | NG burner 60" from wall. Target wall 16' wide, 6'-6" tall w/ steel plates under eave and in window. |
| Specimen | box burner
|
| Ignition | pilot flame
|
| Project ID (s) | |
| Test Director | Maranghides A
|
| Measurement | Value | Uc | Unit |
|---|---|---|---|
| Peak Heat Release Rate, PHRR
|
713
|
38
|
kW
|
| Time to Peak Heat Release Rate
|
21.92
|
0.17
|
min
|
| Total Heat Released, THR
|
742
|
41
|
MJ
|
| Natural Gas Burner Total Heat Released, NGTHR
|
750
|
11
|
MJ
|
| Heat Release Quality Confirmation, HRQC
|
0.997
|
0.057
|
MJ/MJ
|
| Net Specimen Mass (gravimetric), NM = Mi-Mf
|
Not measured | - | kg
|
| Total Fuel Mass Burned, TFM = THR / HOCf
|
14.84
|
0.93
|
kg
|
| Net Effective Heat of Combustion = THR / NM
|
Not measured | - | MJ/kg
|
| O2 Yield = O2 Consumed / TFM
|
3.59
|
0.25
|
kg/kg
|
| CO2 Yield = CO2 Generated / TFM
|
2.73
|
0.20
|
kg/kg
|
| CO Yield = CO Generated / TFM
|
0.00115
|
0.00070
|
kg/kg
|
| Soot Yield = Soot Generated / TFM
|
below detection limit
|
0.0017
|
kg/kg
|
| Baseline Hood Exhaust Flow
|
24.75
|
0.74
|
kg/s
|
| Test Duration = Time(Fire Out) - Time(Ignition)
|
30.90
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
| Parameter | Value | Uc | Unit |
|---|---|---|---|
| Fuel Type
|
Natural Gas
|
- | - |
| Hood Size
|
9
|
- | m
|
| Effective Duct Diameter
|
1.975
|
0.005
|
m
|
| Exhaust Flow Correction Factor
|
1.055
|
0.034
|
- |
| Net Heat of Combustion (per unit mass O2), Ef
|
12.54
|
0.50
|
MJ/kg
|
| Net Heat of Combustion(per unit mass fuel), HOCf
|
50.00
|
1.50
|
MJ/kg
|
| Initial Specimen Mass, Mi (gravimetric)
|
Not measured | - | kg
|
| Final Specimen Mass, Mf (gravimetric)
|
Not measured | - | kg
|
| Event | Time (min) | Description | Video Snapshot Image |
|---|---|---|---|
| 1
|
0.00
|
Ignition
|
|
| peak
|
21.92
|
Peak HRR
|
|
| 2
|
30.90
|
Fire Out
|
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314