| Name | Test026_Mattress_M3-p-two(C1L-p-I1L)_R1
|
|---|---|
| Date | |
| Description | Matress with spring and foam 1" propane flame ignition. 40% Polyurethane foam, 30% Rayon fiber, 14% polyester batting, 13% glass fiber, 3% Olefin batting. 25052g. Camera setting: F4.0,1/60,Gain:0. LED 100% power |
| Specimen | 6" Spring Mattress with two pillows
|
| Ignition | propane wand
|
| Project ID (s) | |
| Test Director | Hamins
|
| Measurement | Value | Uc | Unit |
|---|---|---|---|
| Peak Heat Release Rate, PHRR
|
164
|
10
|
kW
|
| Time to Peak Heat Release Rate
|
4.70
|
0.07
|
min
|
| Total Heat Released, THR
|
82.5
|
7.8
|
MJ
|
| Gas Burner Total Heat Released, NGTHR
|
0
|
- | MJ
|
| Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
| Net Specimen Mass (gravimetric), NM = Mi-Mf
|
5.080
|
0.028
|
kg
|
| Net Effective Heat of Combustion = THR / NM
|
16.2
|
1.5
|
MJ/kg
|
| O2 Yield = O2 Consumed / NM
|
1.228
|
0.040
|
kg/kg
|
| CO2 Yield = CO2 Generated / NM
|
1.448
|
0.053
|
kg/kg
|
| CO Yield = CO Generated / NM
|
0.0757
|
0.0028
|
kg/kg
|
| Soot Yield = Soot Generated / NM
|
0.034
|
0.010
|
kg/kg
|
| Baseline Hood Exhaust Flow
|
19.70
|
0.59
|
kg/s
|
| Test Duration = Time(Fire Out) - Time(Ignition)
|
48.48
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
| Parameter | Value | Uc | Unit |
|---|---|---|---|
| Fuel Type
|
Polyurethane foam / Rayon fiber / polyester batting
|
- | - |
| Hood Size
|
9
|
- | m
|
| Effective Duct Diameter
|
1.975
|
0.005
|
m
|
| Exhaust Flow Correction Factor
|
1.055
|
0.034
|
- |
| Net Heat of Combustion (per unit mass O2), Ef
|
13.10
|
0.52
|
MJ/kg
|
| Net Heat of Combustion(per unit mass fuel), HOCf
|
25.00
|
0.80
|
MJ/kg
|
| Initial Specimen Mass, Mi (gravimetric)
|
25.05
|
0.02
|
kg
|
| Final Specimen Mass, Mf (gravimetric)
|
19.97
|
0.02
|
kg
|
| Event | Time (min) | Description | Video Snapshot Image |
|---|---|---|---|
| 1
|
0.00
|
Ignition
|
|
| 2
|
2.17
|
Flame Dripping
|
|
| peak
|
4.70
|
Peak HRR
|
|
| 3
|
48.42
|
water suppression
|
|
| 4
|
48.48
|
Fire Out
|
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314