Skip to main content
U.S. flag

An official website of the United States government

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Secure .gov websites use HTTPS
A lock ( ) or https:// means you’ve safely connected to the .gov website. Share sensitive information only on official, secure websites.

Validation of and Optimization with a Vapor Compression Cycle Model Accounting for Refrigerant Thermodynamic and Transport Properties

Published

Author(s)

Harrison M. Skye, Piotr A. Domanski, Riccardo Brignoli, SANGHUN LEE, Heunghee Bae

Abstract

CYCLE_D-HX is a semi-theoretical model that simulates the performance of a vapor-compression cycle with forced-convection heat exchangers for specified temperature profiles of the heat source and heat sink. In this study, we validated CYCLE_D-HX using experimental measurements from a small (< 4 kW capacity) heat pump test apparatus operated in cooling mode. We also applied the model to simulate the performance of selected refrigerants in a system with optimized refrigerant circuitries in the evaporator and condenser. The tested refrigerants included the medium-pressure refrigerant R-134a and candidate replacements with a lower global-warming potential (GWP): R-513A, R-450A, R-134a/1234yf/1234ze(E) (49.2/33.8/17.0 mass %), R-515B, and R-1234yf. We also tested high-pressure refrigerant R-410A and candidate replacements with lower-GWP: R-32, R-452B, and R-454B. The model generally agreed with experimental results, with COP and Qvol overpredicted by (0 to 3) % for the basic cycle, and by (0 to 5) % for the cycle with the liquid-line/suction-line heat exchanger (LLSL-HX). Simulations with equal compressor efficiency and optimized tube circuitry showed the COP spread among medium-pressure refrigerants could be reduced to 3 % with proper design, compared to (12 to 33) % from the experiments. In optimized systems, the high-pressure refrigerants' COP was (1 to 6) % higher than the COP of the medium-pressure refrigerants. The LLSL-HX improved performance of refrigerants with high molar heat capacity (here, the medium-pressure refrigerants) by (1.0 to 1.5) %.
Citation
Technical Note (NIST TN) - 2233
Report Number
2233

Keywords

model, CYCLE_D-HX, experimental measurement, Low GWP, refrigerants, air conditioning, heat pump

Citation

Skye, H. , Domanski, P. , Brignoli, R. , Lee, S. and Bae, H. (2022), Validation of and Optimization with a Vapor Compression Cycle Model Accounting for Refrigerant Thermodynamic and Transport Properties, Technical Note (NIST TN), National Institute of Standards and Technology, Gaithersburg, MD, [online], https://doi.org/10.6028/NIST.TN.2233, https://tsapps.nist.gov/publication/get_pdf.cfm?pub_id=935009 (Accessed March 29, 2024)
Created September 2, 2022, Updated November 29, 2022