Smoke Control and Occupant Evacuation at the World Trade Center

Published

Author(s)

M J. Ferreira, S M. Strege, Richard Peacock, Jason D. Averill

Abstract

This paper examines smoke control and occupant evacuation in WTC 1 and WTC 2 on September 11, 2001focusing on the impact region and above for each tower. Approximately 2,000 individuals were at or above the area of impact in WTC 1 and WTC 2 who did not successfully evacuate. NIST found that the smoke management (smoke purge) systems in WTC 1 and WTC 2 were not initiated on September 11,2001. Had the smoke purge sequence (required by the BCNYC for post-fire smoke venting) been initiated in WTC 1or WTC 2, it is unlikely the system would have been capable of operation, due to damage caused by aircraft impacts. Even if fully operational, none of the hypothetical potential smoke management approaches evaluated would have prevented smoke spread given the damage caused by aircraft impact. During the events occurring on September 11, 2001 stair pressurization would have been ineffective in improving conditions for occupants trying to exit the building due to the extensive damage to the stair shafts. Installation of combination fire/smoke dampers in HVAC ductwork, which was not required in WTC 1or WTC 2 at the time the WTC was constructed, may have acted to slow the development of hazardous conditions on the uppermost floors of the building, but would likely not have had a significant effect on the ability of occupants to egress the building due to the impassibility of the exit stairways.
Proceedings Title
Annual Meeting. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (ASHRAE)
Conference Dates
June 21-25, 2008
Conference Location
Salt Lake City, UT, US

Keywords

World Trade Center, smoke control, occupants, evacuation, impact, building collapse, building construction, stairwells, evaluaiton, systems preformance, human response, fire fighters, first responders, damage, management systems, effectiveness, design fires, scenarios

Citation

Ferreira, M. , Strege, S. , Peacock, R. and Averill, J. (2008), Smoke Control and Occupant Evacuation at the World Trade Center, Annual Meeting. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (ASHRAE), Salt Lake City, UT, US, [online], https://tsapps.nist.gov/publication/get_pdf.cfm?pub_id=913101 (Accessed December 3, 2024)