Author(s)
Amanda Pertzborn, Michael Galler
Abstract
In this study, we test the performance of Guideline 36-compliant sequences of operation for the air system and compare the performance to sequences of operation that predate Guideline 36. We present a platform that can be used to study the impact on building operations of changing the control system in a building without changing any other aspect of that building, such as equipment upgrades, internal load variations, and changes to weather. We use the Virtual Cybernetic Building Testbed (VCBT), which contains commercial BACnet-enabled controllers and an operator workstation, as well as the Intelligent Building Agents Laboratory (IBAL), which uses chillers to meet the loads in an air handling unit-variable air volume (AHU-VAV) system and can generate repeatable weather conditions and zone loads. These facilities use a hardware-in-the-loop approach, which combines a simulation of a building with hardware. This is the first demonstration of the combined VCBT-IBAL platform, which provides a method to evaluate potential sequences of operation in hardware before deploying them in real buildings.
Citation
Science and Technology for the Built Environment
Keywords
Guideline 36, HVAC, controls, hardware-in-the-loop
Citation
Pertzborn, A.
and Galler, M.
(2026),
Experimental Comparison of Commercial Implementations of Guideline 36 and Legacy Controller Sequences of Operation, Science and Technology for the Built Environment, [online], https://doi.org/10.1080/23744731.2026.2663718, https://tsapps.nist.gov/publication/get_pdf.cfm?pub_id=960813 (Accessed August 12, 2026)
Additional citation formats
Issues
If you have any questions about this publication or are having problems accessing it, please contact [email protected].