Estimating real-time infiltration for use in residential ventilation control

Published: June 18, 2019

Author(s)

Lisa C. Ng, Stephen M. Zimmerman, Jeremy Good, Brian Tool, Steven J. Emmerich, Andrew K. Persily

Abstract

Minimum outdoor air ventilation rates specified in standards such as ASHRAE Standard 62.2 are generally based on envelope airtightness, building floor area, geographical location, and number of occupants. To meet ventilation requirements in practice, simple on/off controls and operating schedules are most commonly used to maintain the required ventilation rate. Ideally, minimum outdoor ventilation rates should account for unintentional leakage through the building envelope, or "infiltration." ASHRAE Standard 62.2-2016 allows for an infiltration credit, which reduces the required mechanical ventilation. However, infiltration rates vary based on the indoor-outdoor temperature difference, wind, and system operation
Citation: Technical Note (NIST TN) - 2046
Report Number:
2046
NIST Pub Series: Technical Note (NIST TN)
Pub Type: NIST Pubs

Keywords

CONTAM, simplified airflow modeling, residential ventilation, real-time infiltration, energy use, exposure factor, ASHRAE Standard 62.2
Created June 18, 2019, Updated June 18, 2019