Skip to main content
U.S. flag

An official website of the United States government

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Secure .gov websites use HTTPS
A lock ( ) or https:// means you’ve safely connected to the .gov website. Share sensitive information only on official, secure websites.

Estimating real-time infiltration for use in residential ventilation control

Published

Author(s)

Lisa Ng, Stephen M. Zimmerman, Jeremy Good, Brian Tool, Steven Emmerich, Andrew Persily

Abstract

Minimum outdoor air ventilation rates specified in standards such as ASHRAE Standard 62.2 are generally based on envelope airtightness, building floor area, geographical location, and number of occupants. To meet ventilation requirements in practice, simple on/off controls and operating schedules are most commonly used to maintain the required ventilation rate. Ideally, minimum outdoor ventilation rates should account for unintentional leakage through the building envelope, or "infiltration." ASHRAE Standard 62.2-2016 allows for an infiltration credit, which reduces the required mechanical ventilation. However, infiltration rates vary based on the indoor-outdoor temperature difference, wind, and system operation
Citation
Technical Note (NIST TN) - 2046
Report Number
2046

Keywords

CONTAM, simplified airflow modeling, residential ventilation, real-time infiltration, energy use, exposure factor, ASHRAE Standard 62.2

Citation

Ng, L. , Zimmerman, S. , Good, J. , Tool, B. , Emmerich, S. and Persily, A. (2019), Estimating real-time infiltration for use in residential ventilation control, Technical Note (NIST TN), National Institute of Standards and Technology, Gaithersburg, MD, [online], https://doi.org/10.6028/NIST.TN.2046 (Accessed April 26, 2024)
Created June 17, 2019, Updated March 1, 2021