NOTICE: Due to a lapse in annual appropriations, most of this website is not being updated. Learn more.
Form submissions will still be accepted but will not receive responses at this time. Sections of this site for programs using non-appropriated funds (such as NVLAP) or those that are excepted from the shutdown (such as CHIPS and NVD) will continue to be updated.
An official website of the United States government
Here’s how you know
Official websites use .gov
A .gov website belongs to an official government organization in the United States.
Secure .gov websites use HTTPS
A lock (
) or https:// means you’ve safely connected to the .gov website. Share sensitive information only on official, secure websites.
Estimating real-time infiltration for use in residential ventilation control
Published
Author(s)
Lisa Ng, Stephen M. Zimmerman, Jeremy Good, Brian Tool, Steven Emmerich, Andrew Persily
Abstract
Minimum outdoor air ventilation rates specified in standards such as ASHRAE Standard 62.2 are generally based on envelope airtightness, building floor area, geographical location, and number of occupants. To meet ventilation requirements in practice, simple on/off controls and operating schedules are most commonly used to maintain the required ventilation rate. Ideally, minimum outdoor ventilation rates should account for unintentional leakage through the building envelope, or "infiltration." ASHRAE Standard 62.2-2016 allows for an infiltration credit, which reduces the required mechanical ventilation. However, infiltration rates vary based on the indoor-outdoor temperature difference, wind, and system operation
Ng, L.
, Zimmerman, S.
, Good, J.
, Tool, B.
, Emmerich, S.
and Persily, A.
(2019),
Estimating real-time infiltration for use in residential ventilation control, Technical Note (NIST TN), National Institute of Standards and Technology, Gaithersburg, MD, [online], https://doi.org/10.6028/NIST.TN.2046
(Accessed October 8, 2025)