NRC - NIST Intercoparison of Calibration Systems for Current transducers with a voltage output at power frequencies.
Published
Author(s)
Eddy So, R. Arseneau, D. Bennett, Thomas L. Nelson, Bryan C. Waltrip
Abstract
Abstract - A number of international comparisons of current transformer calibrations at power frequencies were conducted in the past. However, all comparisons were done with a secondary current output of 5 A. This inter-comparison of current transformer calibration systems for power frequencies between the National Research Council of Canada and the National Institute of Standards and Technology, USA, was done with a primary current range of 100 A and a non-standard secondary output signal of voltage range of 10 V. The comparison was implemented with a transfer standard consisting of a modified commercial current-comparator-based transimpedance amplifier, based on a development at the National Research Council of Canada, with the output voltage adjustable in magnitude and phase within a range of 11 percent. The results indicate that there are no significant differences in the overall accuracy of calibration systems for current transducers with a voltage output at power frequencies in each laboratory.
Citation
IEEE Transactions on Instrumentation and Measurement
So, E.
, Arseneau, R.
, Bennett, D.
, Nelson, T.
and Waltrip, B.
(2003),
NRC - NIST Intercoparison of Calibration Systems for Current transducers with a voltage output at power frequencies., IEEE Transactions on Instrumentation and Measurement, [online], https://tsapps.nist.gov/publication/get_pdf.cfm?pub_id=30874