| Name | Test_7
|
|---|---|
| Date | |
| Description | Upholstered sofa in 3.7 m by 3.7 m by 2.4 m furnished room. Ignition by 1" propane flame at polyester pillow. Soot sample on roof duct. Flashover observed. |
| Specimen | Polyester fabric sofa w/o barrier in furnished room
|
| Ignition | propane wand
|
| Project ID (s) | |
| Test Director | Zammarano
|
| Measurement | Value | Uc | Unit |
|---|---|---|---|
| Peak Heat Release Rate, PHRR
|
6,076
|
361
|
kW
|
| Time to Peak Heat Release Rate
|
20.22
|
0.07
|
min
|
| Total Heat Released, THR
|
2,269
|
148
|
MJ
|
| Gas Burner Total Heat Released, NGTHR
|
-11
|
- | MJ
|
| Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
| Net Specimen Mass (gravimetric), NM = Mi-Mf
|
Not measured | - | kg
|
| Total Fuel Mass Burned, TFM = THR / HOCf
|
76
|
16
|
kg
|
| Net Effective Heat of Combustion = THR / NM
|
Not measured | - | MJ/kg
|
| O2 Yield = O2 Consumed / TFM
|
2.32
|
0.49
|
kg/kg
|
| CO2 Yield = CO2 Generated / TFM
|
2.90
|
0.62
|
kg/kg
|
| CO Yield = CO Generated / TFM
|
0.050
|
0.011
|
kg/kg
|
| Soot Yield = Soot Generated / TFM
|
0.0107
|
0.0032
|
kg/kg
|
| Baseline Hood Exhaust Flow
|
44.4
|
1.3
|
kg/s
|
| Test Duration = Time(Fire Out) - Time(Ignition)
|
65.68
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
| Parameter | Value | Uc | Unit |
|---|---|---|---|
| Fuel Type
|
Generic
|
- | - |
| Hood Size
|
9
|
- | m
|
| Effective Duct Diameter
|
1.975
|
0.005
|
m
|
| Exhaust Flow Correction Factor
|
1.055
|
0.034
|
- |
| Net Heat of Combustion (per unit mass O2), Ef
|
13.10
|
0.66
|
MJ/kg
|
| Net Heat of Combustion(per unit mass fuel), HOCf
|
30.00
|
6.00
|
MJ/kg
|
| Initial Specimen Mass, Mi (gravimetric)
|
Not measured | - | kg
|
| Final Specimen Mass, Mf (gravimetric)
|
Not measured | - | kg
|
| Event | Time (min) | Description | Video Snapshot Image |
|---|---|---|---|
| 1
|
0.00
|
Ignition
|
|
| 2
|
1.90
|
smoke alarm
|
|
| 3
|
18.75
|
Flashover
|
|
| peak
|
20.22
|
Peak HRR
|
|
| 4
|
62.37
|
water suppression
|
|
| 5
|
65.68
|
Fire Out
|
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)