| Name |                      Test_10 
             | 
          
|---|---|
| Date |                      | 
          
| Description |                      Cabinet #6 burn using 24" line burner with natural gas, vertical orientation inside of cabinet. Burner in Front Right attached to 6 cables bundled vertically with door open.  | 
          
| Specimen |                      Electrical Cables 
             | 
          
| Ignition |                      Line Burner 
             | 
          
| Project ID (s) | |
| Test Director |                      McGrattan 
             | 
          
| Measurement | Value | Uc | Unit | 
|---|---|---|---|
|                      Peak Heat Release Rate, PHRR 
             | 
                                 44.7 
             | 
                                 3.3 
             | 
                                 kW 
             | 
          
|                      Time to Peak Heat Release Rate 
             | 
                                 15.52 
             | 
                                 0.07 
             | 
                                 min 
             | 
          
|                      Total Heat Released, THR 
             | 
                                 36.5 
             | 
                                 3.1 
             | 
                                 MJ 
             | 
          
|                      Gas Burner Total Heat Released, NGTHR 
             | 
                                 13 
             | 
            - |                      MJ 
             | 
          
|                      Heat Release Quality Confirmation, HRQC 
             | 
            Not measured | - |                      MJ/MJ 
             | 
          
|                      Net Specimen Mass (gravimetric), NM = Mi-Mf 
             | 
            Not measured | - |                      kg 
             | 
          
|                      Total Fuel Mass Burned, TFM = THR / HOCf 
             | 
                                   2.16 
             | 
                                   0.20 
             | 
                                   kg 
             | 
            
|                      Net Effective Heat of Combustion = THR / NM 
             | 
            Not measured | - |                      MJ/kg 
             | 
          
|                      O2 Yield = O2 Consumed / TFM 
             | 
                                 1.23 
             | 
                                 0.12 
             | 
                                 kg/kg 
             | 
          
|                      CO2 Yield = CO2 Generated / TFM 
             | 
                                 1.10 
             | 
                                 0.11 
             | 
                                 kg/kg 
             | 
          
|                      CO Yield = CO Generated / TFM 
             | 
                                 0.0267 
             | 
                                 0.0026 
             | 
                                 kg/kg 
             | 
          
|                      Soot Yield = Soot Generated / TFM 
             | 
                                 0.0116 
             | 
                                 0.0019 
             | 
                                 kg/kg 
             | 
          
|                      Baseline Hood Exhaust Flow 
             | 
                                 13.22 
             | 
                                 0.40 
             | 
                                 kg/s 
             | 
          
|                      Test Duration = Time(Fire Out) - Time(Ignition) 
             | 
                                 26.15 
             | 
                                 0.03 
             | 
                                 min 
             | 
          
Uc = Combined Expanded Uncertainty with 95% confidence level
| Parameter | Value | Uc | Unit | 
|---|---|---|---|
|                      Fuel Type 
             | 
                                 PVC, Natural Gas 
             | 
            - | - | 
|                      Hood Size 
             | 
                                 6 
             | 
            - |                      m 
             | 
          
|                      Effective Duct Diameter 
             | 
                                 1.975 
             | 
                                 0.005 
             | 
                                 m 
             | 
          
|                      Exhaust Flow Correction Factor 
             | 
                                 1.055 
             | 
                                 0.034 
             | 
            - | 
|                      Net Heat of Combustion (per unit mass O2), Ef 
             | 
                                 12.84 
             | 
                                 0.51 
             | 
                                 MJ/kg 
             | 
          
|                      Net Heat of Combustion(per unit mass fuel), HOCf 
             | 
                                 16.90 
             | 
                                 0.50 
             | 
                                 MJ/kg 
             | 
          
|                      Initial Specimen Mass, Mi (gravimetric) 
             | 
            Not measured | - |                      kg 
             | 
          
|                      Final Specimen Mass, Mf (gravimetric) 
             | 
            Not measured | - |                      kg 
             | 
          
    | Event | Time (min) | Description | Video Snapshot Image | 
|---|---|---|---|
|                      1 
             | 
                       0.00 
             | 
                       Ignition 
             | 
   
 | 
|                      2 
             | 
                       3.05 
             | 
                       burner gas OFF 
             | 
   
 | 
|                      3 
             | 
                       4.27 
             | 
                       gas back ON 
             | 
   
 | 
|                      peak 
             | 
                       15.52 
             | 
                       Peak HRR 
             | 
   
 | 
|                      4 
             | 
                       26.15 
             | 
                       Fire Out 
             | 
   
 | 
    
    
    
    
    
    Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
        https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
        https://doi.org/10.18434/mds2-2314