| Name |                      Test_01 
             | 
          
|---|---|
| Date |                      | 
          
| Description |                      Cabinet burn using 30 cm box natural gas burner inside of cabinet. Burner in Front Right quadrent.  | 
          
| Specimen |                      Box Burner 
             | 
          
| Ignition |                      pilot flame 
             | 
          
| Project ID (s) | |
| Test Director |                      McGrattan 
             | 
          
| Measurement | Value | Uc | Unit | 
|---|---|---|---|
|                      Peak Heat Release Rate, PHRR 
             | 
                                 543 
             | 
                                 29 
             | 
                                 kW 
             | 
          
|                      Time to Peak Heat Release Rate 
             | 
                                 22.57 
             | 
                                 0.07 
             | 
                                 min 
             | 
          
|                      Total Heat Released, THR 
             | 
                                 363 
             | 
                                 20 
             | 
                                 MJ 
             | 
          
|                      Gas Burner Total Heat Released, NGTHR 
             | 
                                 340.2 
             | 
                                 4.8 
             | 
                                 MJ 
             | 
          
|                      Heat Release Quality Confirmation, HRQC 
             | 
            Not measured | - |                      MJ/MJ 
             | 
          
|                      Net Specimen Mass (gravimetric), NM = Mi-Mf 
             | 
            Not measured | - |                      kg 
             | 
          
|                      Total Fuel Mass Burned, TFM = THR / HOCf 
             | 
                                   7.26 
             | 
                                   0.46 
             | 
                                   kg 
             | 
            
|                      Net Effective Heat of Combustion = THR / NM 
             | 
            Not measured | - |                      MJ/kg 
             | 
          
|                      O2 Yield = O2 Consumed / TFM 
             | 
                                 3.69 
             | 
                                 0.26 
             | 
                                 kg/kg 
             | 
          
|                      CO2 Yield = CO2 Generated / TFM 
             | 
                                 2.86 
             | 
                                 0.21 
             | 
                                 kg/kg 
             | 
          
|                      CO Yield = CO Generated / TFM 
             | 
                                 0.0545 
             | 
                                 0.0040 
             | 
                                 kg/kg 
             | 
          
|                      Soot Yield = Soot Generated / TFM 
             | 
                                 0.0203 
             | 
                                 0.0045 
             | 
                                 kg/kg 
             | 
          
|                      Baseline Hood Exhaust Flow 
             | 
                                 13.95 
             | 
                                 0.42 
             | 
                                 kg/s 
             | 
          
|                      Test Duration = Time(Fire Out) - Time(Ignition) 
             | 
                                 27.90 
             | 
                                 0.03 
             | 
                                 min 
             | 
          
Uc = Combined Expanded Uncertainty with 95% confidence level
| Parameter | Value | Uc | Unit | 
|---|---|---|---|
|                      Fuel Type 
             | 
                                 Natural Gas 
             | 
            - | - | 
|                      Hood Size 
             | 
                                 6 
             | 
            - |                      m 
             | 
          
|                      Effective Duct Diameter 
             | 
                                 1.975 
             | 
                                 0.005 
             | 
                                 m 
             | 
          
|                      Exhaust Flow Correction Factor 
             | 
                                 1.055 
             | 
                                 0.034 
             | 
            - | 
|                      Net Heat of Combustion (per unit mass O2), Ef 
             | 
                                 12.54 
             | 
                                 0.50 
             | 
                                 MJ/kg 
             | 
          
|                      Net Heat of Combustion(per unit mass fuel), HOCf 
             | 
                                 50.00 
             | 
                                 1.50 
             | 
                                 MJ/kg 
             | 
          
|                      Initial Specimen Mass, Mi (gravimetric) 
             | 
            Not measured | - |                      kg 
             | 
          
|                      Final Specimen Mass, Mf (gravimetric) 
             | 
            Not measured | - |                      kg 
             | 
          
    | Event | Time (min) | Description | Video Snapshot Image | 
|---|---|---|---|
|                      1 
             | 
                       0.00 
             | 
                       Ignition 
             | 
   
 | 
|                      peak 
             | 
                       22.57 
             | 
                       Peak HRR 
             | 
   
 | 
|                      2 
             | 
                       23.48 
             | 
                       Gas off 
             | 
   
 | 
|                      3 
             | 
                       27.30 
             | 
                       suppression garden hose 
             | 
   
 | 
|                      4 
             | 
                       27.90 
             | 
                       Fire Out 
             | 
   
 | 
    
    
    
    
    
    Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
        https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
        https://doi.org/10.18434/mds2-2314