| Name | Test14_Redboard_R3
|
|---|---|
| Date | |
| Description | 1/4" thick, 24" wide, 48"tall panels of GPO-3 mounted to 1" thick Marinite board. Ignite using rectangular propane burner @ 60kW for ignition, burner on throughout experiment. No heat flux data |
| Specimen | 1/4" thick, 24" wide, 48" tall panels of GPO-3
|
| Ignition | propane burner
|
| Project ID (s) | |
| Test Director | Leventon
|
| Measurement | Value | Uc | Unit |
|---|---|---|---|
| Peak Heat Release Rate, PHRR
|
109.6
|
7.7
|
kW
|
| Time to Peak Heat Release Rate
|
7.07
|
0.17
|
min
|
| Total Heat Released, THR
|
36.2
|
8.0
|
MJ
|
| Gas Burner Total Heat Released, NGTHR
|
72.1
|
2.2
|
MJ
|
| Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
| Net Specimen Mass (gravimetric), NM = Mi-Mf
|
Not measured | - | kg
|
| Total Fuel Mass Burned, TFM = THR / HOCf
|
2.14
|
0.57
|
kg
|
| Net Effective Heat of Combustion = THR / NM
|
Not measured | - | MJ/kg
|
| O2 Yield = O2 Consumed / TFM
|
3.8
|
1.0
|
kg/kg
|
| CO2 Yield = CO2 Generated / TFM
|
1.75
|
0.47
|
kg/kg
|
| CO Yield = CO Generated / TFM
|
0.084
|
0.023
|
kg/kg
|
| Soot Yield = Soot Generated / TFM
|
0.0102
|
0.0039
|
kg/kg
|
| Baseline Hood Exhaust Flow
|
17.02
|
0.51
|
kg/s
|
| Test Duration = Time(Fire Out) - Time(Ignition)
|
21.48
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
| Parameter | Value | Uc | Unit |
|---|---|---|---|
| Fuel Type
|
Glass-reinforced polyester resin (GPO-3, 'Redboard')
|
- | - |
| Hood Size
|
6
|
- | m
|
| Effective Duct Diameter
|
1.975
|
0.005
|
m
|
| Exhaust Flow Correction Factor
|
1.028
|
0.029
|
- |
| Net Heat of Combustion (per unit mass O2), Ef
|
13.10
|
0.66
|
MJ/kg
|
| Net Heat of Combustion(per unit mass fuel), HOCf
|
16.90
|
2.50
|
MJ/kg
|
| Initial Specimen Mass, Mi (gravimetric)
|
Not measured | - | kg
|
| Final Specimen Mass, Mf (gravimetric)
|
Not measured | - | kg
|
| Event | Time (min) | Description | Video Snapshot Image |
|---|---|---|---|
| 1
|
0.00
|
Ignition
|
|
| peak
|
7.07
|
Peak HRR
|
|
| 2
|
20.00
|
Burner Off
|
|
| 3
|
21.48
|
Fire Out
|
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314