Hoehler, M. Dataset from Fire Safety Challenges of Tall Wood Buildings - Phase 2: Task 3 - Cross Laminated Timber Compartment Fire Tests, 2017 https://doi.org/10.18434/T4/1422512
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019 https://doi.org/10.6028/NIST.TN.207
Experiment Name | Date/Time | Project ID | Project PI | Specimen | Fuel Type | Ignition | Test Duration (min) | Total Heat Released (MJ) | Peak HRR (kW) |
---|---|---|---|---|---|---|---|---|---|
CLT Room Test 1-1 | 2/16/2017 10:10:49 AM | NRCC_CLT | M. Hoehler, J. Su | furnished studio apartment | Cellulose, Plastics | natural gas burner | 135 | 18634.1 | 9886 |
CLT Room Test 1-2 | 2/23/2017 9:49:34 AM | NRCC_CLT | M. Hoehler, J. Su | furnished studio apartment | Cellulose, Plastics | natural gas burner | 108 | 19319.3 | 12974 |
CLT Room Test 1-3 | 3/16/2017 10:19:16 AM | NRCC_CLT | M. Hoehler, J. Su | furnished studio apartment, CLT wall | Cellulose, Plastics | natural gas burner | 247 | 33811.2 | 14766 |
CLT Room Test 1-4 | 3/21/2017 9:51:10 AM | NRCC_CLT | M. Hoehler, J. Su | furnished studio apartment, CLT ceiling | Cellulose, Plastics | natural gas burner | 176 | 37450.5 | 13665 |
CLT Room Test 1-5 | 4/13/2017 9:49:48 AM | NRCC_CLT | M. Hoehler, J. Su | furnished studio apartment, CLT wall | Cellulose, Plastics | natural gas burner | 220 | 55830.6 | 10808 |
CLT Room Test 1-6 | 4/18/2017 9:51:29 AM | NRCC_CLT | M. Hoehler, J. Su | furnished studio apartment, CLT wall and ceiling | Cellulose, Plastics | natural gas burner | 193 | 81484.4 | 13452 |