| Name | Test57_OSB_R3
|
|---|---|
| Date | |
| Description | 7/16" thick, 24" wide, 96"tall panels of OSB mounted to 1" thick Marinite Board. Ignite using propane burner at 65kW, burner continuously. Upper heat flux gauges shielded and exposed once panel is fully involved. |
| Specimen | 7/16" thick, 24" wide, 96" tall panels of OSB
|
| Ignition | propane burner
|
| Project ID (s) | |
| Test Director | Leventon
|
| Measurement | Value | Uc | Unit |
|---|---|---|---|
| Peak Heat Release Rate, PHRR
|
526
|
28
|
kW
|
| Time to Peak Heat Release Rate
|
3.20
|
0.17
|
min
|
| Total Heat Released, THR
|
262
|
18
|
MJ
|
| Gas Burner Total Heat Released, NGTHR
|
43.3
|
1.3
|
MJ
|
| Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
| Net Specimen Mass (gravimetric), NM = Mi-Mf
|
16.15
|
0.28
|
kg
|
| Net Effective Heat of Combustion = THR / NM
|
16.2
|
1.1
|
MJ/kg
|
| O2 Yield = O2 Consumed / NM
|
1.456
|
0.053
|
kg/kg
|
| CO2 Yield = CO2 Generated / NM
|
1.604
|
0.064
|
kg/kg
|
| CO Yield = CO Generated / NM
|
0.0296
|
0.0012
|
kg/kg
|
| Soot Yield = Soot Generated / NM
|
0.00160
|
0.00061
|
kg/kg
|
| Baseline Hood Exhaust Flow
|
18.69
|
0.56
|
kg/s
|
| Test Duration = Time(Fire Out) - Time(Ignition)
|
22.27
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
| Parameter | Value | Uc | Unit |
|---|---|---|---|
| Fuel Type
|
Oriented Strand Board (OSB)
|
- | - |
| Hood Size
|
6
|
- | m
|
| Effective Duct Diameter
|
1.975
|
0.005
|
m
|
| Exhaust Flow Correction Factor
|
1.028
|
0.029
|
- |
| Net Heat of Combustion (per unit mass O2), Ef
|
13.10
|
0.52
|
MJ/kg
|
| Net Heat of Combustion(per unit mass fuel), HOCf
|
30.00
|
0.90
|
MJ/kg
|
| Initial Specimen Mass, Mi (gravimetric)
|
23.39
|
0.20
|
kg
|
| Final Specimen Mass, Mf (gravimetric)
|
7.24
|
0.20
|
kg
|
| Event | Time (min) | Description | Video Snapshot Image |
|---|---|---|---|
| 1
|
0.00
|
Ignition
|
|
| 2
|
2.83
|
unshield heat flux gauges
|
|
| peak
|
3.20
|
Peak HRR
|
|
| 3
|
8.28
|
spray bottle cooling back side of panels
|
|
| 4
|
12.03
|
gas to burner OFF
|
|
| 5
|
20.52
|
pulling off smoldering embers to quench for gravametric measurement
|
|
| 6
|
21.38
|
water suppression of smoldering ember piles
|
|
| 7
|
22.27
|
Fire Out
|
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314