| Name | Test_61
|
|---|---|
| Date | |
| Description | 25 kW-200kW ramp Nat. gas burner in cabinet, ladder style cable tray across top w/ 10 thermoset cables in tray |
| Specimen | Box Burner
|
| Ignition | pilot flame
|
| Project ID (s) | |
| Test Director | McGrattan
|
| Measurement | Value | Uc | Unit |
|---|---|---|---|
| Peak Heat Release Rate, PHRR
|
251
|
14
|
kW
|
| Time to Peak Heat Release Rate
|
15.28
|
0.07
|
min
|
| Total Heat Released, THR
|
103.9
|
6.6
|
MJ
|
| Gas Burner Total Heat Released, NGTHR
|
92.9
|
1.3
|
MJ
|
| Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
| Net Specimen Mass (gravimetric), NM = Mi-Mf
|
Not measured | - | kg
|
| Total Fuel Mass Burned, TFM = THR / HOCf
|
3.46
|
0.24
|
kg
|
| Net Effective Heat of Combustion = THR / NM
|
Not measured | - | MJ/kg
|
| O2 Yield = O2 Consumed / TFM
|
2.16
|
0.17
|
kg/kg
|
| CO2 Yield = CO2 Generated / TFM
|
1.61
|
0.13
|
kg/kg
|
| CO Yield = CO Generated / TFM
|
0.0609
|
0.0048
|
kg/kg
|
| Soot Yield = Soot Generated / TFM
|
Not measured | - | kg/kg
|
| Baseline Hood Exhaust Flow
|
16.62
|
0.50
|
kg/s
|
| Test Duration = Time(Fire Out) - Time(Ignition)
|
15.80
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
| Parameter | Value | Uc | Unit |
|---|---|---|---|
| Fuel Type
|
Natural Gas
|
- | - |
| Hood Size
|
6
|
- | m
|
| Effective Duct Diameter
|
1.975
|
0.005
|
m
|
| Exhaust Flow Correction Factor
|
1.055
|
0.034
|
- |
| Net Heat of Combustion (per unit mass O2), Ef
|
13.10
|
0.52
|
MJ/kg
|
| Net Heat of Combustion(per unit mass fuel), HOCf
|
30.00
|
0.90
|
MJ/kg
|
| Initial Specimen Mass, Mi (gravimetric)
|
Not measured | - | kg
|
| Final Specimen Mass, Mf (gravimetric)
|
Not measured | - | kg
|
| Event | Time (min) | Description | Video Snapshot Image |
|---|---|---|---|
| 1
|
0.00
|
Ignition
|
|
| 2
|
10.37
|
cable tray ignition
|
|
| 3
|
15.27
|
Fuel Off
|
|
| peak
|
15.28
|
Peak HRR
|
|
| 4
|
15.63
|
waer supression
|
|
| 5
|
15.80
|
Fire Out
|
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314