| Name | Test_11
|
|---|---|
| Date | |
| Description | Cabinet #6 burn using 24" line burner with natural gas, vertical orientation inside of cabinet. Burner in Front Right attached to 10 cables bundled vertically with door held closed. |
| Specimen | Electrical Cables
|
| Ignition | Line Burner
|
| Project ID (s) | |
| Test Director | McGrattan
|
| Measurement | Value | Uc | Unit |
|---|---|---|---|
| Peak Heat Release Rate, PHRR
|
30.7
|
2.5
|
kW
|
| Time to Peak Heat Release Rate
|
11.10
|
0.07
|
min
|
| Total Heat Released, THR
|
60.5
|
6.0
|
MJ
|
| Gas Burner Total Heat Released, NGTHR
|
47.60
|
0.68
|
MJ
|
| Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
| Net Specimen Mass (gravimetric), NM = Mi-Mf
|
Not measured | - | kg
|
| Total Fuel Mass Burned, TFM = THR / HOCf
|
3.58
|
0.37
|
kg
|
| Net Effective Heat of Combustion = THR / NM
|
Not measured | - | MJ/kg
|
| O2 Yield = O2 Consumed / TFM
|
1.22
|
0.13
|
kg/kg
|
| CO2 Yield = CO2 Generated / TFM
|
0.877
|
0.096
|
kg/kg
|
| CO Yield = CO Generated / TFM
|
0.094
|
0.010
|
kg/kg
|
| Soot Yield = Soot Generated / TFM
|
0.062
|
0.014
|
kg/kg
|
| Baseline Hood Exhaust Flow
|
13.29
|
0.40
|
kg/s
|
| Test Duration = Time(Fire Out) - Time(Ignition)
|
59.78
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
| Parameter | Value | Uc | Unit |
|---|---|---|---|
| Fuel Type
|
PVC, Natural Gas
|
- | - |
| Hood Size
|
6
|
- | m
|
| Effective Duct Diameter
|
1.975
|
0.005
|
m
|
| Exhaust Flow Correction Factor
|
1.055
|
0.034
|
- |
| Net Heat of Combustion (per unit mass O2), Ef
|
12.84
|
0.51
|
MJ/kg
|
| Net Heat of Combustion(per unit mass fuel), HOCf
|
16.90
|
0.50
|
MJ/kg
|
| Initial Specimen Mass, Mi (gravimetric)
|
Not measured | - | kg
|
| Final Specimen Mass, Mf (gravimetric)
|
Not measured | - | kg
|
| Event | Time (min) | Description | Video Snapshot Image |
|---|---|---|---|
| 1
|
0.00
|
Ignition
|
|
| peak
|
11.10
|
Peak HRR
|
|
| 2
|
15.17
|
Gas rack reduced flow
|
|
| 3
|
26.90
|
gas rack sample stopped due to clogged sample filter
|
|
| 4
|
47.67
|
Increase fire size to 25kW
|
|
| 5
|
52.63
|
gas off
|
|
| 6
|
52.90
|
Fire Out
|
|
| 7
|
59.20
|
open door
|
|
| 8
|
59.78
|
Fire Out
|
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314