Search the title, description, test director, specimen, fuel type, and ignition.
Experiment Name Plot of Heat Release Rate Ignition Photo Date/Time Project Sort ascending Specimen Fuel Type Total Heat Released (MJ) Peak HRR (kW)
Test7_PMMA_R6
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
503
3,579
Test44_Polyiso05_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/2" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
17.9
1,022
Test24_Polyiso_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
32.0
974
Test40_GPO1_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of GPO-1 Glass-reinforced polyester resin (GPO-1)
246
469
Test58_XLPE4_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of XLPE foam (4lb/ft3 density) Cross-linked polyethylene foam (XLPE)
211
3,169
Test8_Redboard_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of GPO-3 Polyester resin (GPO-3, Redboard)
37.8
114.9
Test51_ABS_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of ABS Acrylonitrile Butadiene Styrene (ABS)
566
3,538
Test25_Polyiso_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
gas on
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
31.0
954
Test41_XPSPink2_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 2" thick, 24" wide, 96" tall panels of Pink XPS Foam Extruded Polystyrene Foam (XPS)
100.6
1,687
Test59_XLPE4_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of XLPE foam (4lb/ft3 density) Cross-linked polyethylene foam (XLPE)
149.1
2,876
Test031_ExtensionCord12awg_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) electric cord Plastic
below detection limit
1.02
Test095_RadPallet_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
rad panel ON
Transient Combustion Calorimetry (TCC) pallet Cellulose
below detection limit
0.89
Test047_ShopVac_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic shop vaccum Plastic
below detection limit
1.92
Test063_250mL_Linseed_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) linseed oil Plastic
1.00
1.75
Test015_BigBoxPeanuts2ft_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) cardboard and expanded polystyrene (EPS) peanuts Cellulose, Plastic
38.0
595
Test079_NylonRope_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Nylon rope Nylon
92.0
76.0
Test032_ExtensionCord12awg_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) electric cord Plastic
below detection limit
below detection limit
Test096_RadPallet_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
radiant panel ON (warm up)
Transient Combustion Calorimetry (TCC) pallet Cellulose
below detection limit
below detection limit
Test048_ShopVac_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic shop vaccum Plastic
0.025
2.26
Test064_LinseedOilRags_R0
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) oily rags Plastic
9.71
11.58

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314