Experiment Name | Plot of Heat Release Rate | Ignition Photo | Date/Time | Project Sort descending | Specimen | Fuel Type | Total Heat Released (MJ) | Peak HRR (kW) |
---|---|---|---|---|---|---|---|---|
Test30_Kydex_R2 | Vertical Upward Flamespread on Parallel Panels | 1/4" thick, 24" wide, 96" tall panels of Kydex | Kydex (PVC-acrylic copolymer) | 182
|
1,070
|
|||
Test48_XPSpink1_R3 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of Pink XPS Foam | Extruded Polystyrene Foam (XPS) | 55.3
|
1,332
|
|||
Test1_PMMA_R1 | Vertical Upward Flamespread on Parallel Panels | 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA | Polymethyl methacrylate (PMMA) | 506
|
2,540
|
|||
Test2_PMMA_R2 | Vertical Upward Flamespread on Parallel Panels | 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA | Polymethyl methacrylate (PMMA) | 506
|
2,882
|
|||
Test15_RedCedar_R1 | Vertical Upward Flamespread on Parallel Panels | 7/8" thick, 22.5" wide, 96" tall planks of Western Red Cedar | Western Red Cedar | 139
|
307
|
|||
Test31_Polyiso05_R1 | Vertical Upward Flamespread on Parallel Panels | 1/2" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam | Polyisocyanurate Foam (foil-backed) | 18.6
|
1,056
|
|||
Test49_GPO1_R3 | Vertical Upward Flamespread on Parallel Panels | 1/4" thick, 24" wide, 96" tall panels of GPO-1 | Polyester resin (GPO-1) | 232
|
522
|
|||
Test3_PMMA_R3 | Vertical Upward Flamespread on Parallel Panels | 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA | Polymethyl methacrylate (PMMA) | 506
|
3,197
|
|||
Test16_HDPE_R1 | Vertical Upward Flamespread on Parallel Panels | 1/4" thick, 24" wide, 96" tall panels of HDPE | High Density Polyethelyne (HDPE) | 284
|
2,817
|
|||
Test32_Polyiso05_R2 | Vertical Upward Flamespread on Parallel Panels | 1/2" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam | Polyisocyanurate Foam (foil-backed) | 18.2
|
997
|
|||
Test50_POMGF_R2 | Vertical Upward Flamespread on Parallel Panels | 1/4" thick, 24" wide, 96" tall panels of POM-GF | Polyoxymethylene (POM-GF) | 367
|
540
|
|||
Test13_PVC_R2 | Vertical Upward Flamespread on Parallel Panels | 1/4" thick, 24" wide, 96" tall panels of PVC | Polyvinyl chloride (PVC) | 84.0
|
236
|
|||
Test17_GPO1_R1 | Vertical Upward Flamespread on Parallel Panels | 1/4" thick, 24" wide, 96" tall panels of GPO-1 | Polyester resin (GPO-1) | 235
|
498
|
|||
Test33_XPSpink1_R1 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of Pink XPS Foam | Extruded Polystyrene Foam (XPS) | 50.4
|
812
|
|||
Test14_Redboard_R3 | Vertical Upward Flamespread on Parallel Panels | 1/4" thick, 24" wide, 48" tall panels of GPO-3 | Glass-reinforced polyester resin (GPO-3, 'Redboard') | 36.2
|
109.6
|
|||
NGQC_6m_20kgs_3MW | Vertical Upward Flamespread on Parallel Panels | tube gas burner | Natural Gas | 2,127
|
3,022
|
|||
Test34_XPSgreen1_R1 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of Green XPS Foam | Extruded Polystyrene Foam (XPS) | 54.9
|
1,255
|
|||
BurnerShakedown21 | Vertical Upward Flamespread on Parallel Panels | Sand Burner | Propane | 22.9
|
71.0
|
|||
Test18_XLPE2_R1 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of XLPE Foam (2lb/ft3 density) | Cross-linked polyethylene foam (XLPE) | 101.4
|
3,992
|
|||
Test53_ABS_R3 | Vertical Upward Flamespread on Parallel Panels | 1/4" thick, 24" wide, 96" tall panels of ABS | Acrylonitrile Butadiene Styrene (ABS) | 550
|
3,541
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314