Experiment Name Plot of Heat Release Rate Ignition Photo Date/Time Project Specimen Fuel Type Total Heat Released (MJ) Sort descending Peak HRR (kW)
HeptanePoolConfirmationBurn
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
pouring fuel into pans
Structure Separation Experiments: Shed Burns without Wind Pool Burner Heptane
362
2,487
Test50_POMGF_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of POM-GF Polyoxymethylene (POM-GF)
367
540
Test30_2trashCanRagsPaper_r1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry plastic trashcan filled with cotton rags and paper Cellulose, Plastic
370
462
Test12_PBT_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of PBT Polybutylene terephthalate (PBT)
375
2,821
NGQC_3m_3kgs_500kW
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Natural Gas Confirmation Burner box gas burner Natural Gas
381
532
Test28_POMGF_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of POM-GF Polyoxymethylene (POM-GF)
387
503
NGQC_3m_3kgs_500kW_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Natural Gas Confirmation Burner Tube Burner Natural Gas
403
552
Test35_8boxRags_r1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry cardboard boxes filled with cotton rags Cellulose
433
290
Test34_4box_r2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry cardboard boxes filled with paper Cellulose
442
288
Test61_POMGF_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of POM-GF Polyoxymethylene (POM-GF)
452
536
Test39_4trashcan_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry trashcans filled with paper Cellulose, Plastic
453
705
Test37_4box_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry cardboard boxes filled with paper Cellulose
459
930
Test38_4box_R4
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry cardboard boxes filled with paper Cellulose
471
1,964
Test3_4box_r1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry cardboard boxes filled with paper Cellulose
479
944
Test5_2Pallet_r1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Multiple Item Transient Combustion Calorimetry wood pallets and paper Cellulose
502
934
Test7_PMMA_R6
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
503
3,579
Test4_PMMA_R4
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
504
3,140
Test46_HIPS_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
NTP Time Query Failed!
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of HIPS High Impact Polystyrene (HIPS)
504
3,228
Test5_PMMA_R5
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
504
3,166
Test2_PMMA_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
506
2,882

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)