Skip to main content
U.S. flag

An official website of the United States government

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Secure .gov websites use HTTPS
A lock ( ) or https:// means you’ve safely connected to the .gov website. Share sensitive information only on official, secure websites.

FCD Experiments

Search the title, description, test director, specimen, fuel type, and ignition.
Experiment Name Plot of Heat Release Rate Ignition Photo Date/Time Project Sort ascending Specimen Fuel Type Total Heat Released (MJ) Peak HRR (kW)
Test7_PMMA_R6
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
503
3,579
Test44_Polyiso05_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/2" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
17.9
1,022
Test24_Polyiso_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
32.0
974
Test40_GPO1_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of GPO-1 Glass-reinforced polyester resin (GPO-1)
246
469
Test58_XLPE4_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of XLPE foam (4lb/ft3 density) Cross-linked polyethylene foam (XLPE)
211
3,169
Test59_XLPE4_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of XLPE foam (4lb/ft3 density) Cross-linked polyethylene foam (XLPE)
149.1
2,876
Test8_Redboard_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of GPO-3 Polyester resin (GPO-3, Redboard)
37.8
114.9
Test51_ABS_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of ABS Acrylonitrile Butadiene Styrene (ABS)
566
3,538
Test25_Polyiso_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
gas on
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
31.0
954
Test41_XPSPink2_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 2" thick, 24" wide, 96" tall panels of Pink XPS Foam Extruded Polystyrene Foam (XPS)
100.6
1,687
Test60_XLPE4_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of XLPE foam (4lb/ft3 density) Cross-linked polyethylene foam (XLPE)
174.4
2,830
Test9_SIS_wire_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 90 vertically oriented strands of SIS wire XLPE (SIS Wire)
16.0
132.8
Test52_HIPS_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of HIPS High Impact Polystyrene (HIPS)
535
3,094
Test26_Polyiso2_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
gas on
Vertical Upward Flamespread on Parallel Panels 2" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
37.6
784
Test42_XPSGreen2_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 2" thick, 24" wide, 96" tall panels of Green XPS Foam Extruded Polystyrene Foam (XPS)
105
1,946
Test61_POMGF_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of POM-GF Polyoxymethylene (POM-GF)
452
536
Test10_SIS_wire_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 96 vertically oriented strands of SIS wire attached to 1/4" thick, 24" wide, 96"tall panels of GPO-3 XLPE (SIS Wire) and (GPO-3)
47
142
Test63_XPSpink2_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 2" thick, 24" wide, 96" tall panels of Pink XPS Foam Extruded Polystyrene Foam (XPS)
93.2
1,580
Test27_Polyiso2_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
gas on
Vertical Upward Flamespread on Parallel Panels 2" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
38.8
801
Test45_HIPS_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of HIPS High Impact Polystyrene (HIPS)
509
2,955

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)