Skip to main content
U.S. flag

An official website of the United States government

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Secure .gov websites use HTTPS
A lock ( ) or https:// means you’ve safely connected to the .gov website. Share sensitive information only on official, secure websites.

FCD Experiments

Search the title, description, test director, specimen, fuel type, and ignition.
Experiment Name Plot of Heat Release Rate Ignition Photo Date/Time Project Sort ascending Specimen Fuel Type Total Heat Released (MJ) Peak HRR (kW)
Test32_Polyiso05_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/2" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam Polyisocyanurate Foam (foil-backed)
18.2
997
Test50_POMGF_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of POM-GF Polyoxymethylene (POM-GF)
367
540
Test3_PMMA_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
506
3,197
Test16_HDPE_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of HDPE High Density Polyethelyne (HDPE)
284
2,817
Test33_XPSpink1_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of Pink XPS Foam Extruded Polystyrene Foam (XPS)
50.4
812
Test13_PVC_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of PVC Polyvinyl chloride (PVC)
84.0
236
Test17_GPO1_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of GPO-1 Polyester resin (GPO-1)
235
498
NGQC_6m_20kgs_3MW
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels tube gas burner Natural Gas
2,127
3,022
Test34_XPSgreen1_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of Green XPS Foam Extruded Polystyrene Foam (XPS)
54.9
1,255
BurnerShakedown21
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels Sand Burner Propane
22.9
71.0
Test14_Redboard_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 48" tall panels of GPO-3 Glass-reinforced polyester resin (GPO-3, 'Redboard')
36.2
109.6
Test53_ABS_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of ABS Acrylonitrile Butadiene Styrene (ABS)
550
3,541
Test18_XLPE2_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of XLPE Foam (2lb/ft3 density) Cross-linked polyethylene foam (XLPE)
101.4
3,992
Test54_XPSpink2_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 2" thick, 24" wide, 96" tall panels of Pink XPS Foam Extruded Polystyrene Foam (XPS)
84.5
1,510
Test19_XLPE6_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of XLPE Foam (6lb/ft3 density) Cross-linked polyethylene foam (XLPE)
278
3,500
Test20_OSB_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 7/16" thick, 24" wide, 96" tall panels of OSB Oriented Strand Board (OSB)
243
622
Test37_OSB_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 7/16" thick, 24" wide, 96" tall panels of OSB Oriented Strand Board (OSB)
243
894
Test55_XPSgreen2_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 2" thick, 24" wide, 96" tall panels of Green XPS Foam Extruded Polystyrene Foam (XPS)
110
1,839
Test4_PMMA_R4
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1/4" thick, 24" wide, 96" tall panels of cast Black PMMA Polymethyl methacrylate (PMMA)
504
3,140
Test35_XPSpink1_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Vertical Upward Flamespread on Parallel Panels 1" thick, 24" wide, 96" tall panels of Pink XPS Foam Extruded Polystyrene Foam (XPS)
47.1
1,080

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314