Experiment Name Plot of Heat Release Rate Ignition Photo Date/Time Project Specimen Sort ascending Fuel Type Total Heat Released (MJ) Peak HRR (kW)
Test052_FRtarp15x10_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic tarp Plastic
54.4
83.0
Test046_ShopVac_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic shop vaccum Plastic
295
545
Test047_ShopVac_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic shop vaccum Plastic
below detection limit
1.92
Test048_ShopVac_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic shop vaccum Plastic
0.025
2.26
Test049_ShopVac_R4
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic shop vaccum Plastic
308
534
Test073_PlasticStanchion_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic pole Plastic
42.6
69.3
Test074_PlasticStanchion_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic pole Plastic
36.4
48.2
Test075_PlasticStanchion_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic pole Plastic
36.8
49.4
Test085_PatioChair_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic chair Plastic
102.6
159.9
Test086_PatioChair_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic chair Plastic
103.9
208
Test084_PatioChair_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic chair Plastic
103.7
209
Test076_PlasticChain_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic chain Plastic
below detection limit
1.84
Test077_PlasticChain_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic chain Plastic
32.1
30.1
Test078_PlasticChain_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic chain Plastic
26.2
21.3
Test027_BlowerDuct_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic air duct Plastic
0.424
9.05
Test028_BlowerDuct_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic air duct Plastic
0.480
6.15
Test029_BlowerDuct_R3
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) Plastic air duct Plastic
0.282
5.20
Test093_Pallet_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) pallet Cellulose
0.71
2.11
Test094_Pallet_R2
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
Transient Combustion Calorimetry (TCC) pallet Cellulose
1.16
2.58
Test095_RadPallet_R1
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
rad panel ON
Transient Combustion Calorimetry (TCC) pallet Cellulose
below detection limit
0.89

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)