Name | CornerTest1
|
---|---|
Date | |
Description | Mockup room corner test of furniture ignition for CLT project with NRCC. Shelf loading with pine crib stick and kitchen table with 6 chairs. 12 ft corner with 8ft ceiling and no soffit. Ignite with 50 kW natural gas burner |
Specimen | room corner mockup
|
Ignition | natural gas burner
|
Project ID (s) | |
Test Director | Hoehler
|
Measurement | Value | Uc | Unit |
---|---|---|---|
Peak Heat Release Rate, PHRR
|
1,624
|
98
|
kW
|
Time to Peak Heat Release Rate
|
25.07
|
0.17
|
min
|
Total Heat Released, THR
|
1,522
|
96
|
MJ
|
Natural Gas Burner Total Heat Released, NGTHR
|
42.27
|
0.60
|
MJ
|
Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
Net Specimen Mass (gravimetric), NM = Mi-Mf
|
Not measured | - | kg
|
Total Fuel Mass Burned, TFM = THR / HOCf
|
76.5
|
9.0
|
kg
|
Net Effective Heat of Combustion = THR / NM
|
Not measured | - | MJ/kg
|
O2 Yield = O2 Consumed / TFM
|
1.52
|
0.19
|
kg/kg
|
CO2 Yield = CO2 Generated / TFM
|
1.95
|
0.24
|
kg/kg
|
CO Yield = CO Generated / TFM
|
0.0267
|
0.0033
|
kg/kg
|
Soot Yield = Soot Generated / TFM
|
Not measured | - | kg/kg
|
Baseline Hood Exhaust Flow
|
24.95
|
0.75
|
kg/s
|
Test Duration = Time(Fire Out) - Time(Ignition)
|
49.50
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
Parameter | Value | Uc | Unit |
---|---|---|---|
Fuel Type
|
Cellulose, Plastic
|
- | - |
Hood Size
|
6
|
- | m
|
Effective Duct Diameter
|
1.975
|
0.005
|
m
|
Exhaust Flow Correction Factor
|
1.000
|
0.029
|
- |
Net Heat of Combustion (per unit mass O2), Ef
|
13.10
|
0.66
|
MJ/kg
|
Net Heat of Combustion(per unit mass fuel), HOCf
|
19.90
|
2.00
|
MJ/kg
|
Initial Specimen Mass, Mi (gravimetric)
|
Not measured | - | kg
|
Final Specimen Mass, Mf (gravimetric)
|
Not measured | - | kg
|
Event | Time (min) | Description | Video Snapshot Image |
---|---|---|---|
1
|
0.00
|
Ignition
|
|
2
|
12.65
|
chair ignition
|
|
3
|
12.95
|
Gas burner off
|
|
4
|
14.60
|
Table ignition
|
|
5
|
24.32
|
all chairs ignited
|
|
peak
|
25.07
|
Peak HRR
|
|
6
|
29.97
|
table collapse
|
|
7
|
38.98
|
start water suppression
|
|
8
|
49.50
|
Fire Out
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314