Skip to main content
U.S. flag

An official website of the United States government

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Secure .gov websites use HTTPS
A lock ( ) or https:// means you’ve safely connected to the .gov website. Share sensitive information only on official, secure websites.

Refrigerant Migration in a Split-Unit Air Conditioner

Published

Author(s)

W. J. Mulroy, David Didion

Abstract

The relationship between cyclic refrigerant migration and cyclic loss for a residential, split-system air conditioner has been investigated. The cyclic refrigerant migration was measured at different points in the operating cycle by simultaneously shutting five pneumatically operated valves that isolated the refrigerant in the major system components. The refrigerant was then removed, weighed, and returned to the system. The unit tested was found to have a high initial increasing capacity as trapped refrigerant was returned to the system fmm the accumulator. The unit performance was also compared to single and double time constant regressive approximations and to the time constant calculated from the evaporator mass and heat transfer coefficient. Although relationships between migrated refrigerant and cyclic capacity were observed, no practical refrigerant migration test method that would be less burdensome than the cyclic tests of ASHRAE Standard 116 appears possible at this time.
Citation
ASHRAE Transactions
Volume
91
Issue
No. 1A

Keywords

refrigerants, air conditioning, valves, standards, tests, degradation, test facilities, valves, equations

Citation

Mulroy, W. and Didion, D. (1985), Refrigerant Migration in a Split-Unit Air Conditioner, ASHRAE Transactions, [online], https://tsapps.nist.gov/publication/get_pdf.cfm?pub_id=910739 (Accessed October 11, 2024)

Issues

If you have any questions about this publication or are having problems accessing it, please contact reflib@nist.gov.

Created January 1, 1985, Updated February 19, 2017