Temperature Uncertainties for Bare-Bead and Aspirated Thermocouple Measurements in Fire Environments

Published

Author(s)

William M. Pitts, E Braun, Richard D. Peacock, Henri E. Mitler, Erik L. Johnsson, Paul A. Reneke, L G. Blevins

Abstract

Temperature measurements have been made for natural-gas and heptane fires in a reduced-scale enclosure using a variety of bare-bead and aspirated thermocouples in order to characterize the uncertainties. The focus is the role of radiative heat transfer and the effects of finite time response on the measurements. The findings show that significant errors are possible for all thermocouples considered. Aspirated thermocouples reduce, but do not eliminate, such uncertainties. An alternate approach, use of several bare-bead thermocouples with extrapolation to zero diameter, is not easily implemented in the time-varying temperature environments characteristic of fires.
Proceedings Title
14th Joint Panel Meeting
Conference Dates
May 28-June 3, 1998
Conference Location
Tsukuba
Conference Title
Thermal Measurments: The Foundation of Fire Standards, ASTM STP 1427

Keywords

aspirated thermocouples, enclosure, fire tests, measurement uncertainties, temperature measurements, thermocouples

Citation

Pitts, W. , Braun, E. , Peacock, R. , Mitler, H. , Johnsson, E. , Reneke, P. and Blevins, L. (2003), Temperature Uncertainties for Bare-Bead and Aspirated Thermocouple Measurements in Fire Environments, 14th Joint Panel Meeting, Tsukuba, -1, [online], https://tsapps.nist.gov/publication/get_pdf.cfm?pub_id=861103 (Accessed March 29, 2024)