Skip to main content
U.S. flag

An official website of the United States government

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Secure .gov websites use HTTPS
A lock ( ) or https:// means you’ve safely connected to the .gov website. Share sensitive information only on official, secure websites.

Improving the Performance of a Roof Top Air-Conditioning Unit by Refrigerant Circuitry Optimization

Published

Author(s)

David A. Yashar, Sunil Lee

Abstract

This study demonstrates the performance improvement of an air-to-air roof top unit (RTU) achieved by optimizing an evaporator’s refrigerant circuitry using evolutionary algorithms. The subject of this study is a unit with a cooling capacity of 7.5 Tons (26.4 kW). The RTU employs two separate refrigerant cycles having separate compressors, condensers, and thermostatic expansion valves (TXV) but using a single evaporator slab in which two separate refrigerant circuits are implemented. We modified the RTU by replacing the refrigerant-to-air condensers with water cooled brazed plate heat exchangers in order to facilitate testing. Performance tests were conducted in a conditioned environmental chamber in line with AHRI standard 340/360; in order to accomplish this, we maintained the liquid line saturation pressure and subcooling from the manufacturer’s test data by adjusting the condenser water flow rate and temperature. We also measured the in-situ air velocity profile using Particle Image Velocimetry (PIV), a non-intrusive, laser-based technique. The measurements showed that the range of air velocities passing through the heat exchanger varied from 0.5 ms-1 to 3.0 ms-1, with the integrated average of the measurements being 1.75 ms-1. The PIV data was used to generate a map of the air flow distribution through the heat exchanger, which served as the basis for refrigerant circuitry optimization. We simulated the performance of the original evaporator using the measured air velocity distribution and NIST’s heat exchanger model, EVAP-COND, and were able to tune our computational model to exactly match the laboratory measurements. We then used the measured air velocity distribution with NIST’s evolutionary algorithm optimization module, Intelligent System for Heat Exchanger Design (ISHED), to redesign the evaporator circuitry. The optimization process resulted in a design with a simulated capacity nearly 8 % higher than the original design. The RTU manufacture
Citation
Technical Note (NIST TN) - 1806
Report Number
1806

Keywords

Air Velocity Profile, Roof Top Air Conditioning Unit, Particle Image Velocimetry (PIV), Circuitry optimization

Citation

Yashar, D. and Lee, S. (2013), Improving the Performance of a Roof Top Air-Conditioning Unit by Refrigerant Circuitry Optimization, Technical Note (NIST TN), National Institute of Standards and Technology, Gaithersburg, MD, [online], https://doi.org/10.6028/NIST.TN.1806 (Accessed March 28, 2024)
Created August 2, 2013, Updated November 10, 2018