Experiment Name | Plot of Heat Release Rate | Ignition Photo | Date/Time | Project | Specimen Sort descending | Fuel Type | Total Heat Released (MJ) | Peak HRR (kW) |
---|---|---|---|---|---|---|---|---|
Methanol_1m_Pool_R1 | Characteristics of a 1 m Methanol Pool Fire | 1 m diameter pool burner | Methanol | 753
|
282
|
|||
Methanol_1m_Pool_R2 | Characteristics of a 1 m Methanol Pool Fire | 1 m diameter pool burner | Methanol | 1,243
|
279
|
|||
Test36_XPSgreen1_R2 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of Green XPS Foam | Extruded Polystyrene Foam (XPS) | 49.1
|
628
|
|||
Test62_XPSgreen1_R3 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of Green XPS Foam | Extruded Polystyrene Foam (XPS) | 22.9
|
174
|
|||
Test34_XPSgreen1_R1 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of Green XPS Foam | Extruded Polystyrene Foam (XPS) | 54.9
|
1,255
|
|||
Test35_XPSpink1_R2 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of Pink XPS Foam | Extruded Polystyrene Foam (XPS) | 47.1
|
1,080
|
|||
Test48_XPSpink1_R3 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of Pink XPS Foam | Extruded Polystyrene Foam (XPS) | 55.3
|
1,332
|
|||
Test33_XPSpink1_R1 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of Pink XPS Foam | Extruded Polystyrene Foam (XPS) | 50.4
|
812
|
|||
Test21_Polyiso_R1 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam | Polyisocyanurate Foam (foil-backed) | 28.6
|
949
|
|||
Test24_Polyiso_R2 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam | Polyisocyanurate Foam (foil-backed) | 32.0
|
974
|
|||
Test25_Polyiso_R3 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam | Polyisocyanurate Foam (foil-backed) | 31.0
|
954
|
|||
Test23_XLPE2_R2 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of XLPE Foam (2lb/ft3 density) | Cross-linked polyethylene foam (XLPE) | 104.9
|
4,186
|
|||
Test18_XLPE2_R1 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of XLPE Foam (2lb/ft3 density) | Cross-linked polyethylene foam (XLPE) | 101.4
|
3,992
|
|||
Test58_XLPE4_R1 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of XLPE foam (4lb/ft3 density) | Cross-linked polyethylene foam (XLPE) | 211
|
3,169
|
|||
Test59_XLPE4_R2 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of XLPE foam (4lb/ft3 density) | Cross-linked polyethylene foam (XLPE) | 149.1
|
2,876
|
|||
Test60_XLPE4_R3 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of XLPE foam (4lb/ft3 density) | Cross-linked polyethylene foam (XLPE) | 174.4
|
2,830
|
|||
Test38_XLPE6_R2 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of XLPE Foam (6lb/ft3 density) | Cross-linked polyethylene foam (XLPE) | 280
|
3,459
|
|||
Test39_XLPE6_R3 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of XLPE Foam (6lb/ft3 density) | Cross-linked polyethylene foam (XLPE) | 301
|
3,427
|
|||
Test19_XLPE6_R1 | Vertical Upward Flamespread on Parallel Panels | 1" thick, 24" wide, 96" tall panels of XLPE Foam (6lb/ft3 density) | Cross-linked polyethylene foam (XLPE) | 278
|
3,500
|
|||
Test44_Polyiso05_R3 | Vertical Upward Flamespread on Parallel Panels | 1/2" thick, 24" wide, 96" tall panels of Polyisocyanurate Foam | Polyisocyanurate Foam (foil-backed) | 17.9
|
1,022
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314